Watlow D4T Data Logger
•
69
•
Chapter 5 Function Reference
Options:
• True Good
: output true (on) and no output error
• True Bad
: output true (on) and output error
• False Good
: output false (off) and no output error
• False Bad
: output false (off) and output error
Less Than
The output (T/F) is on when receiver A is less than B.
Signals
Direction
Label
Type
Function
Receiver
A
Analog
Signal to be compared to B
B
Analog
Signal to be compared to A
Transmitter
T/F
Digital
On when A is less than B, otherwise off
Function
To test if A is less than B, set Function to
Less Than
.
Error Handling
When an error exists on any receiver, the function cannot definitively determine the result of
the comparison and an error will be generated. Use Error Handling to select the output's val-
ue and error status.
Options:
• True Good
: outputs value is true (on) with no error
• True Bad
: outputs value is true (on) and has an error
• False Good
: outputs value is false (off) with no error
• False Bad
: outputs value is false (off) and has an error
Equal To
The output (T/F) is on when receivers A and B are equal to each other. See Tolerance.
Signals
Direction
Label
Type
Function
Receiver
A
Analog
Signal to be compared to B
B
Analog
Signal to be compared to A
Transmitter
T/F
Digital
On when A and B are equal and within tolerance, otherwise
off
Function
To test if A and B are equal to each other, set Function to
Equal To
.