Watlow Controls 

EHG SL 10 User’s Manual

Navigating the Series EHG SL 10 with the Front Panel

The three-character display normally shows the process 
temperature. Press the Mode Key once to view the Set 
Point value. The right decimal point will illuminate 
when viewing the Set Point value. Press the Up-Arrow 
or Down-Arrow Key to change the Set Point. Press the 
Mode Key again to return to the process temperature 
display. Otherwise the display will automatically return 
to showing the process temperature after three seconds.

To view or change parameter values, hold down 

both the Up-Arrow and Down-Arrow Keys for five 

seconds. This will display the Set Point High Limit 
prompt. Press the Mode Key to view the other param-
eter prompts. Press the Up-Arrow or Down-Arrow Key 
once to view a parameter’s value. Press the Up-Arrow 
or Down-Arrow Key to increase or decrease that value. 
Press the Mode Key to again display the prompt and 
again to display the next prompt. Press the Mode Key 
at the Display Build Number prompt to return to the 
process value display.

Display

Parameter Name & Description

Range

Default

Access

Set Point

Set the set point.

0°C (32°F) to Set Point High Limit

150°C (302°F)

read/write

[SLA]

Set Point High Limit Alarm

Set the temperature at which the limit will turn off 
the heater.

0 to 220°C (32 to 428°F)

200°C (392°F)

read/write

[HtA]

High Temperature Alert (Above Set Point)

Set the high temperature that will trigger an alert.

1 to 99°C (2 to 178°F)

20°C (36°F)

read/write

[LtA]

Low Temperature Alert (Below Set Point)

Set the low temperature that will trigger an alert.

5 to 99°C (9 to 178°F)

20°C (36°F)

read/write

[Cnt]

Control Mode Select

Select a control method.

[onF]

 on-off

[PId]

 PID

[onF]

 on-off

read/write

[HyS]

On-Off Hysteresis

Set the how far below the set point the temperature 
can drop before the heater turns on.

3 to 28°C (5 to 50°F)

3°C (6°F)

read/write

[`Pb]

Proportional Band

Set the proportional band.

0 to 68°C (0 to 122°F)

0°C or F

read/write

[Int]

Integral

Set the integral value.

0 to 999

0

read/write

[dEu]

Derivative

Set the derivative value.

0 to 999

0

read/write

[`Ct]

Cycle Time

Set the cycle time.

5 to 60

10

read/write

[Abt]

Ambient Temperature

View the ambient temperature.

read only

[Adr]

Modbus Device Address

View the controller release version.

1 to 247

1

read/write

[bAU]

Modbus Baud Rate

Select the communication speed.

[`96]

 9,600

[192]

 19,200

[384]

 38,400

[`96]

 9,600

read/write

[`tU]

Temperature Units

Select the temperature scale.

F

C

C

read/write

[bru]

Base Release Version

View the controller’s base release version.

read only

[bPu]

Base Prototype Version

View the controller’s base prototype version.

read only

[bbu]

Base Build Number

View the controller’s base build number.

read only

[dru]

Display Release Version

View the interface’s release version.

read only

[dPu]

Display Prototype Version

View the interface’s prototype version.

read only

[dbu]

Display Build Number

View the interface’s build number.

read only