Watlow EZ-ZONE
®
ST
•
63
•
Chapter 6 Factory Page
Control Module • Factory Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
No Dis-
play
Diagnostics
Hardware ID
Display hardware ID.
17 or 31
Instance 1
Map 1 Map 2
0
0
0x65
(101)
1
1
- - - - 1001
Inst. 1
- - - -
dint
R
No Dis-
play
Diagnostics
Software ID
Display software ID.
0 to 2147483647
- - - -
Instance 1
Map 1 Map 2
2
2
0x65
(101)
1
2
- - - - 1002
Inst. 1
- - - -
dint
R
No Dis-
play
Diagnostics
Device Name
0 or 32
EZ-
ZONE
ST
Instance 1
Map 1 Map 2
0
0
0x65
(101)
1
0x0B(11)
- - - - 1011
Inst. 1
- - - -
string
RWE
No Dis-
play
Diagnostics
Device Status
OK (138)
FAIL (32)
- - - -
Instance 1
Map 1 Map 2
18
30
0x65
(101)
1
0x0A(10)
- - - - 1016
Inst. 1
- - - -
uint
R
[`CAL]
[FCty]
Calibration Menu
[`Mu]
[ Mv]
Calibration (1 to 2)
Electrical Measure-
ment
Read the raw elec-
trical value for this
input in the units
corresponding to the
Sensor Type (Setup
Page, Analog Input
Menu) setting.
-3.4e38 to 3.4e38
Instance 1
Map 1 Map 2
309
400
Instance 2
Map 1 Map 2
311
490
0x68
(104)
1 to 2
0x15
(21)
- - - - 4021
Inst. 1
400
Inst. 2
560
float
R
[ELi;o]
[ELi.o]
Calibration (1 to 2)
Electrical Input
Offset
Change this value to
calibrate the low end
of the input range.
-1,999.000 to 9,999.000
0.0
Instance 1
Map 1 Map 2
47
378
Instance 2
Map 1 Map 2
75
468
0x68
(104)
1 to 2
0xA (10)
- - - - 4010
Inst. 1
378
Inst. 2
538
float
RWES
[ELi;S]
[ELi.S]
Calibration (1 to 2)
Electrical Input
Slope
Adjust this value to
calibrate the slope of
the input value.
-1,999.000 to 9,999.000
1.0
Instance 1
Map 1 Map 2
49
380
Instance 2
Map 1 Map 2
77
470
0x68
(104)
1 to 2
0xB (11)
- - - - 4011
Inst. 1
380
Inst. 2
540
float
RWES
[ELo;o]
[ELo.o]
Calibration (1)
Electrical Output
Offset
Change this value to
calibrate the low end
of the output range.
-1,999.000 to 9,999.000
0.0
Instance 1
Map 1 Map 2
- - - -
788
0x76
(118)
1
5
- - - - 18005
- - - -
float
RWES
[ELo;S]
[ELo.S]
Calibration (1)
Electrical Output
Slope
Adjust this value to
calibrate the slope of
the output value.
-1,999.000 to 9,999.000
1.0
Instance 1
Map 1 Map 2
- - - -
790
0x76
(118)
1
6
- - - - 18006 - - - - float
RWES
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with another interface
.
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EE-
PROM
S: User
Set