Watlow EZ-ZONE
®
ST
•
31
•
Chapter 3 Operations Page
Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
& Read/
Write
[``Ai]
[oPEr]
Analog Input Menu
[``Ain]
[ Ain]
Analog Input (1 to 2)
Process Value
View the process value.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1 Map 2
- - - -
360
Instance 2
Map 1 Map 2
- - - -
450-
0x68 (104)
1 to 2
1
0
4001
Inst. 1
360
Inst. 2
520
float
R
No Dis-
play
Analog Input (1 to 2)
Filtered Process Value
View the filtered process
value.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1 Map 2
- - - -
402
Instance 2
Map 1 Map 2
- - - -
492-
0x68 (104)
1 to 2
0x16 (22)
0
4022
Inst. 1
402
Inst. 2
562
float
R
No Dis-
play
Analog Input (1)
Ambient Temperature
View ambient temperature.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1 Map 2
34
366
Instance 2
Map 1 Map 2
- - - -
492-
0x68 (104)
1
4
0
4004
Inst. 1
402
Inst. 2
562
float
R
[`i;Er]
[ i.Er]
Analog Input (1 to 2)
Error Status
View the cause of the most
recent error. If the
[Attn]
message is
[Er;i1]
or
[Er;i2]
, this parameter will
display the cause of the in-
put error.
[nonE]
None (61)
[OPEn]
Open (65)
[Shrt]
Shorted (127)
[`E;M]
Measurement Er-
ror (149)
[E;CAL]
Bad Calibration
Data (139)
[Er;Ab]
Ambient Error (9)
[E;;Rtd]
RTD Error (141)
[FAiL]
Fail (32)
[NSrc]
Not Sourced (146)
None
Instance 1
Map 1 Map 2
41
362
Instance 2
Map 1 Map 2
69
452
0x68 (104)
1 to 2
2
1
4002
Inst. 1
362
Inst. 2
522
uint
R
No Dis-
play
Analog Input (1)
Clear Latched Input Er-
ror
Clear latched input.
Clear (0)
No Change (255)
Instance 1
Map 1 Map 2
68
416
Instance 2
Map 1 Map 2
96
506
0x68 (104)
1
0x1D (29)
0
4029
Inst. 1
416
uint
W
[`i;Ca]
[ i.CA]
Analog Input (1 to 2)
Calibration Offset
Offset the input reading to
compensate for lead wire re-
sistance or other factors that
cause the input reading to
vary from the actual process
value.
-1,999.000 to 9,999.000°F
or units
-1,110.555 to 5,555.000°C
0.0
Instance 1
Map 1 Map 2
51
382
Instance 2
Map 1 Map 2
79
472
0x68 (104)
1 to 2
0xC (12)
2
4012
Inst. 1
382
Inst. 2
542
float
RWES
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EE-
PROM
S: User
Set