Watlow EZ-ZONE
®
ST
•
36
•
Chapter 3 Operations Page
Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
& Read/
Write
No Dis-
play
Alarm (1 to 2)
Alarm Silenced
Indicates if alarm can be
silenced.
Yes (106)
No (59)
- - - -
Instance 1
Map 1 Map 2
1500 1900
Instance 2
Map 1 Map 2
1550
1960
0x6D
(109)
1 to 4
0x0B (11)
- - - -
9011
Inst. 1
1500
Inst. 2
1550
uint
R
No Dis-
play
Alarm (1 to 2)
Alarm Latched
Indicates if alarm is
latched.
Yes (106)
No (59)
- - - -
Instance 1
Map 1 Map 2
1498 1898
Instance 2
Map 1 Map 2
1548
1958
0x6D
(109)
1 to 4
0x0A (10)
- - - -
9010
Inst. 1
1498
Inst. 2
1548
uint
R
[CUrr]]
[oPEr]]
Current Menu
Note:
To use the current sensing feature, Time Base (Setup Page, Output
Menu) must be set to 0 .7 seconds or more
.
[`C;hi]
[ C.hi]
Current (1)
High Set Point
Set the current value that
will trigger a high heater
error state.
-1,999.000 to 9,999.000
50.0
Instance 1
Map 1 Map 2
286
1254
0x73
(115)
1
8
- - - -
15008
Inst. 1
1134
float
RWES
[`C;Lo]
[ C.Lo]
Current (1)
Low Set Point
Set the current value that
will trigger a low heater er-
ror state.
-1,999.000 to 9,999.000
0.0
Instance 1
Map 1 Map 2
288
1256
0x73
(115)
1
9
- - - -
15009
Inst. 1
1136
float
RWES
[`CU;r]
[ CU.r]
Current (1)
Read
View the most recent cur-
rent value monitored by the
current transformer.
-1,999.000 to 9,999.000
Instance 1
Map 1 Map 2
38
1240
0x73
(115)
1
1
- - - -
15001
Inst. 1
- - - -
float
R
[`C;Er]
[ C.Er]
Current (1)
SSR Error
View the cause of the most
recent load fault.
[nonE]
None (61)
[Shrt]
Shorted (127)
[open]
Open (65)
None
Instance 1
Map 1 Map 2
40
1242
0x73
(115)
1
2
- - - -
15002
Inst. 1
1122
uint
R
[`h;Er]
[ h.Er]
Current (1)
Heater Error
View the cause of the most
recent load fault monitored
by the current transformer.
[nonE]
None (61)
[high]
High (37)
[Low]
Low (53)
None
Instance 1
Map 1 Map 2
282
1244
0x73
(115)
1
3
- - - -
15003
Inst. 1
1124
uint
R
No Dis-
play
Current (1)
Error Status
View the cause of the most
recent load fault
[none]
None (61)
[fail]
Fail (32)
- - - -
Instance 1
Map 1 Map 2
1160 1400
0x73
(115)
1
21
- - - -
15021
- - - - uint
R
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EE-
PROM
S: User
Set