Watlow EZ-ZONE
®
ST
•
40
•
Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[``Ai]
[`Set]
Analog Input Menu
[`Sen]
[ SEn]
Analog Input (1 to 2)
Sensor Type
Set the analog sensor type
to match the device wired
to this input.
Note:
There is no open-
sensor detection
for process inputs .
[`oFF]
Off (62)
[``tC]
Thermocouple (95)
[`mu]
Millivolts (56)
[uolT]
Volts dc (104)
[`MA]
Milliamps dc (112)
[r0;1H]
RTD 100 Ω (113)
[r1;0H]
RTD 1,000 Ω (114)
Instance 1
Map 1 Map 2
42
368
Instance 2
Map 1 Map 2
70
458
0x68 (104)
1 to 2
5
3
4005
Inst. 1
368
Inst. 2
528
uint
RWES
[`Lin]
[ Lin]
Analog Input (1 to 2)
Linearization
Set the linearization to
match the thermocouple
wired to this input.
[```J]
J (46)
[```F]
F (30)
[```E]
E (26)
[```d]
D (23)
[```C]
C (15)
[```b]
B (11)
[```t]
T (93)
[```S]
S (84)
[```r]
R (80)
[```n]
N (58)
[```H]
K (48)
J
Instance 1
Map 1 Map 2
43
370
Instance 2
Map 1 Map 2
71
460
0x68 (104)
1 to 2
6
4
4006
Inst. 1
370
Inst. 2
530
uint
RWES
[`Rt;L]
[ rt.L]
Analog Input (1 to 2)
RTD Leads
Set to match the number
of leads on the RTD wired
to this input.
[```2]
2 (1)
[```3]
3 (2)
2
Instance 1
Map 1 Map 2
44
372
Instance 2
Map 1 Map 2
72
462
0x68 (104)
1 to 2
7
- - - -
4007
Inst. 1
372
Inst. 2
532
uint
RWES
[Unit]
[Unit]
Analog Input (1 to 2)
Units
Set the type of units the
sensor will measure.
[`A;tP]
Absolute Temperature
(1540)
[``rh]
Relative Humidity
(1538)
[`Pro]
Process (75)
[PWr]
Power (73)
Process
Instance 1
Map 1 Map 2
- - - -
442
Instance 2
Map 1 Map 2
- - - - 532
0x68 (104)
1 to 2
0x2A (42)
5
4042
- - - - uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EE-
PROM
S:
User
Set
To go to the Setup Page from the Home Page, press both
the Up
¿
and Down
¯
keys for six seconds.
[``Ai]
will
appear in the upper display and
[`Set]
will appear in
the lower display.
• Press the Up
¿
or Down
¯
key to move through
the menus.
• Press the Advance Key
‰
to move to a submenu.
• Press the Up
¿
or Down
¯
key to move through
the submenus.
• Press the Advance Key
‰
to move through the pa-
rameters of the menu or submenu.
• Press the Infinity Key
ˆ
to move backwards
through the levels: parameter to submenu; sub-
menu to menu; menu to Home Page.
• Press and hold the Infinity Key
ˆ
for two seconds
to return to the Home Page.
Note:
Avoid continuous writes within loops . Excessive writes to EEPROM
will cause premature EEPROM failure . The EEPROM is rated for
1,000,000 writes . Navigate to Setup Page under the CoM menu and
set prompt Non-volatile Save
[`nU;S]
to No .