Watlow EZ-ZONE
®
ST
•
42
•
Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[`i;Er]
[ i.Er]
Analog Input (1 to 2)
Error Latching
Turn input error latching
on or off. If latching is on,
errors must be manually
cleared.
[`off]
Off (62)
[``on]
On (63)
Off
Instance 1
Map 1 Map 2
67
414
Instance 2
Map 1 Map 2
95
504
0x68 (104)
1 to 2
0x1C (28)
- - - -
4028
Inst. 1
414
Inst. 2
574
uint
RWES
[`dEC]
[ dEC]
Analog Input (1 to 2)
Display Precision
Set the precision of the
displayed value.
[```0]
Whole (105)
[``0;0]
Tenths (94)
[`0;00]
Hundredths (40)
[0;000]
Thousandths (96)
Whole
Instance 1
Map 1 Map 2
- - - -
398
Instance 2
Map 1 Map 2
- - - - 488
0x68 (104)
1 to 2
0x14 (20)
- - - -
4020
Inst. 1
398
Inst. 2
558
uint
RWES
[`s;ba]
[ S.bA]
Analog Input (1 to 2)
Sensor Backup
Enable sensor backup.
[`off]
Off (62)
[``on]
On (63)
Off
Instance 1
Map 1 Map 2
65
410
Instance 2
Map 1 Map 2
93
500
0x68 (104)
1 to 2
0x1A (26)
- - - -
4026
Inst. 1
410
Inst. 2
570
uint
RWES
[`dio]
[`Set]
Digital Input/Output Menu
[`dir]
[ dir]
Digital Input/Output (5
or 6)
Direction
Set this function to oper-
ate as an input or output.
[OtPt]
Output (68)
[``in]
Input Voltage (193)
[iCon]
Input Dry Contact (44)
Output
Instance 5
Map 1 Map 2
169
1060
Instance 6
Map 1 Map 2
182
1090
0x6A
(106)
5 to 6
1
82
6001
Inst. 5
1000
Inst. 6
1030
uint
RWES
[``Fn]
[ Fn]
Digital Output (5 or 6)
Function
Select what function will
drive this output.
[`oFF]
Off (62)
[heat]
Heat, Control Loop
(36)
[cool]
Cool, Control Loop (20)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[LiM]
Limit (126)
[ALM]
Alarm (6)
Instance 5
Map 1 Map 2
173
1068
Instance 6
Map 1 Map 2
186
1098
0x 6A
(106)
5 to 6
5
83
6005
Inst. 5
1008
Inst. 6
1068
uint
RWES
[``Fi]
[ Fi]
Digital Output (5 or 6)
Function Instance
Set the instance of the
function selected above.
1 or 2
1
Instance 5
Map 1 Map 2
174
1070
Instance 6
Map 1 Map 2
187
1100
0x6A
(106)
5 to 6
6
84
6006
Inst. 5
1010
Inst. 6
1040
uint
RWES
[`o;Ct]
[ o.Ct]
Digital Output (5 or 6)
Control
Set the output control
type. This parameter
is only used with PID
control, but can be set
anytime.
[`Ftb]
Fixed Time Base (34)
[`utb]
Variable Time Base
(103)
Fixed
Time
Base
Instance 5
Map 1 Map 2
170
1062
Instance 6
Map 1 Map 2
183
1092
0x6A
(106)
5 to 6
2
85
6002
Inst. 5
1002
Inst. 6
1032
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EE-
PROM
S:
User
Set