Watlow EZ-ZONE
®
ST
•
47
•
Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[`h;SP]
[ h.SP]
Control Loop (1)
Set Point Closed Limit
High
Set the high end of the set
point range.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
9,999°F or
units
5,537°C
Instance 1
Map 1 Map 2
197
1896
0x6B
(107)
1
4
53
7004
Inst. 1
2166
float
RWES
[SP;Lo]
[SP.Lo]
Control Loop (1)
Set Point Open Limit
Low
Set the minimum value
of the open-loop set point
range.
-100.0 to 100.0%
-100
Instance 1
Map 1 Map 2
199
1898
0x6B
(107)
1
5
54
7005
Inst. 1
2168
float
RWES
[SP;hi]
[SP.hi]
Control Loop (1)
Set Point Open Limit
High
Set the maximum value
of the open-loop set point
range.
-100.0 to 100.0%
100
Instance 1
Map 1 Map 2
201
1900
0x6B
(107)
1
6
55
7006
Inst. 1
2170
float
RWES
[otpt]
[`Set]
Output Menu
[``Fn]
[ Fn]
Output (1 to 4)
Function
Select what function will
drive this output.
[`oFF]
Off (62)
[ALM]
Alarm (6)
[heat]
Heat, Control Loop
(36)
[Cool]
Cool, Control Loop (20)
[LiM]
Limit (126)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
off
Instance 1
Map 1 Map 2
134
948
[Map1 Offset
+ 13]
[Map2 Offset
+ 30]
0x6A
(106)
1 to 4
5
83
6005
Inst. 1
888
Offset
+ 30
uint
RWES
[``Fi]
[ Fi]
Output (1 to 4)
Function Instance
Set the instance of the
function selected above.
1 to 4
1
Instance 1
Map 1 Map 2
135
950
[Map1 Offset
+ 13]
[Map2 Offset
+ 30]
0x6A
(106)
1 to 4
6
84
6006
Inst. 1
890
Offset
+ 30
uint
RWES
[`o;Ct]
[ o.Ct]
Output (1 to 4)
Control
Set the output control
type. This parameter
is only used with PID
control, but can be set
anytime.
[`Ftb]
Fixed Time Base (34)
[`utb]
Variable Time Base
(103)
Fixed
Time
Base
Instance 1
Map 1 Map 2
131
942
[Map1 Offset
+ 13]
[Map2 Offset
+ 30]
0x6A
(106)
1 to 4
2
85
6002
Inst. 1
882
Offset
+ 30
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EE-
PROM
S:
User
Set