Chapter 5 Profile Page
Profile Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index Par ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[Ent1]
[Ent1]
Step (1 to 40)
Event 1
Select whether Event Out-
put 1 is on, unchanged or
off during this step.
[`oFF]
Off (62)
[Ucgd]
Unchanged (1557)
[``on]
On (63)
Off
Instance 1
Map 1 Map 2
508
4012
[Map1 Offset
+ 20]
[Map2 Offset
+ 100]
0x79
(121)
1 to (40)
7
- - - -
21007
Inst. 1
2882
Offset
+80
uint
RWE
[Ent2]
[Ent2]
Step (1 to 40)
Event 2
Select whether Event Out-
put 2 is on, unchanged or
off during this step.
[`oFF]
Off (62)
[Ucgd]
Unchanged (1557)
[``on]
On (63)
Off
Instance 1
Map 1 Map 2
509
4014
[Map1 Offset
+ 20]
[Map2 Offset
+ 100]
0x79
(121)
1 to (40)
8
- - - -
21008
Inst. 1
2884
Offset
+80
uint
RWE
No Dis-
play
Step (1 to 40)
Event Input 1
Current state of digital
input 5.
Off (62)
On (63)
- - - -
Instance 1
Map 1 Map 2
- - - - 3866
0x7A
(122)
1
0x22 (34)
- - - -
22034
Inst. 1
- - - -
uint
R
No Dis-
play
Step (1 to 40)
Event Input 2
Current state of digital
input 6.
Off (62)
On (63)
- - - -
Instance 1
Map 1 Map 2
- - - - 3868
0x7A
(122)
1
0x23 (35)
- - - -
22035
Inst. 1
- - - -
uint
R
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read
with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EE-
PROM
S: User
Set
Display
Step Type
Description
Parameters in Step Type
[``ti]
[ ti]
Step Types
Time
A Time Step controls at the Target Set Point and maintains
two event output states for the designated time.
[tg;SP]
Target Set Point
[hoUr]
Hours
[Min]
Minutes
[`SEC]
Seconds
[Ent1]
Event Output 1
[Ent2]
Event Output 2
[rAtE]
[rAtE]
Step Types
Rate
A Rate Step ramps the process value to the Target Set Point
in degrees per minute while maintaining two event output
states.
[tg;SP]
Target Set Point
[rAtE]
Rate
[Ent1]
Event Output 1
[Ent2]
Event Output 2
[`W;E]
[ W.E]
Step Types
Wait For Event
A Wait Event Step will wait for the event input states to
match the two Wait Event settings.
[WE;1]
Wait Event 1 (digital input 5)
[WE;2]
Wait Event 2 (digital input 6)
[Ent1]
Event Output 1
[Ent2]
Event Output 2
[W;Pr]
[W.Pr]
Step Types
Wait For Process
A Wait For Process Step will wait for the process value to
match the Wait For Process value.
[WPr]
Wait For Process Instance
[WP1]
Wait For Process Value
[Ent1]
Event Output 1
[Ent2]
Event Output 2
[w;bo]
[W.bo]
Step Types
Wait For Both
A Wait For Both will wait for the process value to match the
Wait For Process value and the Event Step will wait for the
event input states to match the two Wait Event settings.
[W;P1]
Wait For Process Value
[WE;1]
Wait Event 1 (digital input 5)
[WE;2]
Wait Event 2 (digital input 6)
[Ent1]
Event Output 1
[Ent2]
Event Output 2