Watlow F4T Install & Troubleshooting
•
22
•
Chapter 2 Install and Wire
Output Connections
(cont .)
Six Digital Outputs (High Density)
FMHA - CAAA - A _ _ _
Internal
Common
open collector/switched dc
B1
D1
D2
D3
D4
D5
D6
Z1
Supply
open collector/switched dc
open collector/switched dc
open collector/switched dc
open collector/switched dc
open collector/switched dc
Open Collector
• Maximum switched voltage is 32V
Î
(dc)
• 400mA, maximum open circuit volt-
age of 25V
Î
(dc), typical 8V
Î
(dc)
at 80mA
• Maximum output sink current per
output is 1.5A (external class 2 or
*SELV supply required)
• Total sink current for all outputs not
to exceed 8A
• Do not connect outputs in parallel
• *Safety Extra Low Voltage
Switched DC
• User selectable voltage, 5V
Î
(dc) at
130mA or 19 to 22V
Î
(dc) at 80mA
Open Collector Outputs
B1
Z1
D6
D5
D4
D3
D2
D1
24Vdc
Switched DC Outputs
B1
Z1
D6
D5
D4
D3
D2
D1
5Vdc
24Vdc
User Selectable
Voltage
Digital Output - Switched DC Wiring Example
Note:
As a switched DC output; this output is a constant current output delivering 750 mW, cur-
rent limited to 150 mA. The internal supply is 5V(dc) open circuit. Pin Z1 is shared to all
digital outputs. This type of output is meant to drive solid state relays, not mechanical
Internal Supply
+
+
+
-
-
-
DC90-60C0-0000
Htr 3
Htr 2
Htr 1
B1
Z1
D6
D5
D4
D3
D2
D1
5Vdc
24Vdc
User Selectable
Voltage
Anderson-Bolds ~ 216-360-9800
www.anderson-bolds.com