Watlow F4T Install & Troubleshooting
•
50
•
Chapter 6 Appendix
•
Input Type
Max Error @
25 Deg C
Accuracy
Range Low
Accuracy
Range High
Units
J
±1.75
0
750
Deg C
K
±2.45
-200
1250
Deg C
T (-200 to 350)
±1.55
-200
350
Deg C
N
±2.25
0
1250
Deg C
E
±2.10
-200
900
Deg C
R
±3.9
0
1450
Deg C
S
±3.9
0
1450
Deg C
B
±2.66
870
1700
Deg C
C
±3.32
0
2315
Deg C
D
±3.32
0
2315
Deg C
F (PTII)
±2.34
0
1343
Deg C
RTD, 100 ohm
±2.00
-200
800
Deg C
RTD, 1000 ohm
±2.00
-200
800
Deg C
mV
±0.05
0
50
mV
Volts
±0.01
0
10
Volts
mAdc
±0.02
2
20
mAmps DC
mAac
±5
-50
50
mAmps AC
Potentiometer,
1K range
±1
0
1000
Ohms
Operating Range
Input Type
Range Low
Range High
J
-210
°C
1200
°C
K
-270
°C
1371
°C
T
-270
°C
400
°C
N
-270
°C
1300
°C
E
-270
°C
1000
°C
R
-50
°C
1767
°C
S
-50
°C
1767
°C
B
-50
°C
1816
°C
C
0
°C
2315
°C
D
0
°C
2315
°C
F (PTII)
0
°C
1343
°C
RTD (100 ohm)
-200
°C
800
°C
RTD (1000 ohm)
-200
°C
800
°C
mV
-50
50
Volts
0
10
Anderson-Bolds ~ 216-360-9800