Document #10-32813 Rev A; June 07, 2019
Page
65
of 69
Key
Value
Feature
Definition
LogIntervalSec
integer of 1-
86,400
5 by default
Data Logging
This applies to models RMAP-XX
D
X-XXXX. This key defines the data log
interval in seconds, entered as an integer with a range of 1 – 86,400
seconds. Any value outside this range is clipped.
Setup Key: LogIntervalSec
Key
Value
Feature Definition
ModbusRtu6 nor:\Gateway\ModbusRtu6.csv
Modbus®
RTU
This is only available if the model number is RMAP-2XXX-XXXX.
Full file name / path where the Modbus® RTU 6 field bus gateway
file lives. This file associates Modbus® RTU registers with data
points from any of the 3 remaining busses when Modbus® RTU 6 is
configured as a slave.
Setup Key: Modbus® RTU6
Key
Value
Feature Definition
ModbusRtu7 nor:\Gateway\ModbusRtu7.csv
Modbus®
RTU
This is only available if the model number is RMAP-2XXX-XXXX.
Full file name / path where the Modbus® RTU 7 field bus gateway
file lives. This file associates Modbus® RTU registers with data
points from any of the three remaining busses when Modbus® RTU
7 is configured as a slave.
Setup Key: Modbus® RTU7
Key
Value
Feature Definition
ModbusTCP nor:\Gateway\ModbusTcp.csv
Modbus®
TCP
Server
Full file name / path where the Modbus® TCP field bus gateway file
lives. This file associates Modbus® TCP registers with data points
from any of the four local busses.
Setup Key: Modbus® TCP
Key
Values
Feature Definition
RtuFc6 0 (FALSE) = Master
uses Function
Code 16 exclus-
ively
1 (TRUE) = Master
uses Function
Code 6 for single
register writes
Modbus®
RTU Func-
tion Code
6
This is only available for model number RMAP-
2X
XX-XXXX.
This is used to enable Modbus® RTU Function Code 6 (Write Single Register) on
master channels for devices that do not implement Modbus® Function Code 16
(Write Multiple Registers). It is only necessary if the RMA PLUS does not negotiate
this requirement on its own.
This record is not a member of the default file, and therefore, the feature is disabled.
To enable the feature, you must add this record to the setup file.
Setup Key: RTU Fc6