 is a feature of the Auto ON mode. When both relays are 

manually turned OFF the PW holds the lights OFF until no motion has been 
detected for the duration of the Time Delay. With subsequent occupancy, the PW 
turns the load ON. If both relays are ON and one relay is manually turned OFF 
this relay remains OFF until both the Time Delay and retrigger delay expires for 
the relay that is ON, after that time the ON Mode control settings again apply.

INSTALLATION

1.  Make sure that the power has been turned OFF at the circuit breaker.

2.  Connect wires to the PW flying leads as shown in the 

wiring diagram. 

The ground wire (green) must be 

fastened to ground for the sensor to work properly.

 

3.   Attach the sensor to the wall box by inserting screws into 

the two wide holes on the top and bottom of the attached 
metal bracket. Match them up with the holes in the wall 
box and tighten.

4.   Turn the circuit breaker ON. Wait one minute, then push the Auto ON/OFF 

switch for each load and the lights will turn ON. There is a delay due to initial 
power-up of the sensor that only occurs during installation.

5. Test and adjust the sensor if necessary.

6.  Attach the cover plate.

#12 – #14 AWG

Cu Wire Only

Strip Gage

1/2"

12.7mm

Visit our website for FAQs: www.wattstopper.com

WARNING

TURN THE POWER OFF AT THE CIRCUIT BREAKER

BEFORE INSTALLING THE SENSOR OR WORKING ON THE LOAD.

Ground

PW-203

PW-203

Junction Box

Junction Box

Black (Line)

Red (Load 1)

Brown (Load 2)

Blue (Line)

White (Neutral)

Yellow (Traveler)

Load 1

Load 2

1

2

120-277V 50/60Hz

White (Neutral)

Black (Line)

PW-203 Wiring

 

Important:  

Wire the remote unit to the same branch circuit as the main unit 

controlling the load. If relay 2 of the main unit cannot be controlled from the 
remote unit, check wiring to be sure both units are on the same branch circuit.

 Caution: 

 

Do not install this device if there is not at least 10 meters (30 feet) or 

more of wire between the unit and the electrical service panel.

Summary of Contents for PW-203

Page 1: ...c or electronic ballast Horsepower Rating each relay 1 6 HP 120VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec for 10 min with DIP switch setting PIR Adjustment High or Low DIP switch Light Level Adjustment 8fc to 180 fc Alerts Selectable Audible Visual Cover plate not included US Patents 5640113 6617560 PW 203 Passive Infrared Mult...

Page 2: ...ccupancy turns ON all the lights that are connected to the same circuit The occupant can turn OFF the load at any time by pressing the ON OFF button of any sensor that is connected to the circuit If the occupant forgets to turn OFF the lights the last sensor to detect occupancy turns them all OFF after the time delay expires A walk through mode can turn lights OFF after only 3 minutes if no activi...

Page 3: ...egree field of view The red LED on the sensor flashes when the PIR detects motion Masking the lens Opaque adhesive tape is supplied so that sections of the PIR sensor s view can be masked This allows you to eliminate coverage in unwanted areas Since masking removes bands of coverage remember to take this into account when troubleshooting coverage problems PIR Coverage 7 5 2 2m 15 4 5m 20 6 1m 35 10 ...

Page 4: ...e first 30 seconds If motion continues beyond the first 30 seconds the set time delay applies High DIP 5 OFF Default setting Suitable for most applications PIR Sensitivity Adjustment The PW sensor constantly monitors the controlled environment and automatically adjusts the PIR to avoid common ambient conditions that can cause false detections while providing maximum coverage Reduces sensitivity by...

Page 5: ...ings provided No Audible Alerts DIP 7 OFF With an ON Mode DIP switch in the OFF position the load turns ON and OFF automatically based on occupancy If the load is turned OFF manually Presentation Mode operation applies This prevents the load from turning ON automatically after it was deliberately turned OFF Pressing the button to turn lights ON returns the sensor to Auto ON mode Switch 9 default i...

Page 6: ...ll box and tighten 4 Turn the circuit breaker ON Wait one minute then push the Auto ON OFF switch for each load and the lights will turn ON There is a delay due to initial power up of the sensor that only occurs during installation 5 Test and adjust the sensor if necessary 6 Attach the cover plate 12 14 AWG Cu Wire Only Strip Gage 1 2 12 7mm Visit our website for FAQs www wattstopper com WARNING T...

Page 7: ...e aid of artificial light In order to set this as the threshold level of brightness so that the artificial lights remain OFF perform the following steps 1 Make sure the room is lit appropriately 2 Put the sensor into TEST mode using the Time Delay DIP switches 3 Press and hold the ON OFF button Relay 1 button on the PW 203 for 3 seconds until you hear a beep 4 Step away from the sensor After 25 se...

Page 8: ... 7 Disabled Enabled Audible Alert 4 Disabled Enabled Walk Through 9 1 2 3 4 5 6 7 8 Time Delay Walk Through ON Relay 1 Mode Relay 2 Mode Audible Alerts PIR Sensitivity Visible Alerts Test 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes Service 5 minutes 1 2 3 Time Delay Service bypasses occupancy light level functions Control the load manually using ON OFF button 6 Disabled Enabled Visible ...

Page 9: ...t turn ON call 800 879 8585 for technical support Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify proper operation set DIP switch 1 to ON then reset switches 1 2 and 3 to OFF to start Test Mode Move out of view of the sensor The lights should turn OFF in approximately 5 seconds 2 Verify that the sensor is mounted at least six feet 2 me...

Page 10: ...t damages with respect to loss of property revenue or profit or cost of removal installation or reinstallation 2800 De La Cruz Boulevard Santa Clara CA 95050 Technical Support 800 879 8585 www wattstopper com 10188r2 9 2010 Please Recycle COVER PLATES WattStopper PW series wall switches fit behind industry standard decorator style switch cover plates Units come in the following colors which are in...

Reviews: