Auto-Zone Plus
Section 3
Programming
3-33
Constant Volume AHU
Status
Line 1 Displays the currently selected CVAHU and its current operating software version
on all Status Screens shown below.
Status Screen #1
Status Screen #2
CVAHU # 18 vl.xx
Occupied Mode
Neutral Mode
Line 2 -
Unoccupied Mode
Occupied Mode
Holiday Active
Push Button Override
Forced Occupied
Forced Unoccupied
Forced Fan Only Mode
Line 3 -
Neutral Mode
Cooling Mode
Heating Mode
Line 4 -
(Reserved for Future Use)
This Line is Blank
CVAHU # 18 vl.xx
Temperature: 78.6
°
F
CSP 75.0
°
HSP 72.0
°
Slide Adjust.:
0.0
°
Line 2 -
Displays the current Zone Temperature.
Line 3 -
Displays the currently active Cooling
Setpoint (CSP) and Heating Setpoint (HSP)
Line 4 -
Displays the current effect the optional
Sensor Slide Adjust has on the Heating and
Cooling Setpoints
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...