Auto-Zone Plus
Section 3
Programming
3-41
Setpoint Screen #12
Setpoint Screen #13
Setpoint Screen #14
CVAHU Setpoints
Economizer Setpoints
Min Position: 10 %
Control Rate: 90
The
Min Econo %
is the position the economizer holds during
occupied mode when it is not enabled for operation, due to
Outdoor Air or Wetbulb Temperature.
During economizer control, the economizer damper is allowed
to move 1 percent open or closed, as required, at a rate equal to
this value. Use this to speed up or slow down the operation of
your economizer.
Minimum
Default
Maximum
Min Position
0 %
10 %
100 %
Control Rate
0
90
100
CVAHU Setpoints
Economizer Setpoints
Min Voltage: 0.0 v
Max Voltage: 10.0 v
The user can set the voltages required to open and close the
damper. Some actuators use a 2-10 vdc signal instead of 0-10
vdc.
If the system is not configured for Economizer Control, no
economizer setpoint screens will appear.
Minimum
Default
Maximum
Min Voltage
0.0 VDC
0.0 VDC
10.0 VDC
Max Voltage
0.0 VDC
10.0 VDC
10.0 VDC
CVAHU Setpoints
Fan Starting Delay
Multiplier...: 10
If there are several air handling units on a system and you
don’t want them to all start at the same when going into the
occupied mode or after a power outage, you can input a
Fan
Starting Multiplier
. The multiplier is multiplied times the
address number of the unit and this becomes the number of
seconds this unit waits before starting the fan. For example if
the Multiplier is 5 and this unit is at address #18, then the time
delay will be 90 seconds.
Minimum
Default
Maximum
Multiplier
0
0
30
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...