Section 4
Auto-Zone Plus
4-8
Start-Up and Troubleshooting
1.3
Troubleshooting
1.3.1
Checking the CommLink II Network Loop
Diagram
Overview
This test checks for proper Network loop voltages at the CommLink II.
Tip
The Loop LED (located on the front panel) should “flicker” when the CommLink II is
attempting to communicate. The Loop LED will flicker more noticeably for a few
seconds when first powered up. If the Loop LED does not flicker, the unit is defective.
Proper loop voltages are essential for reliable communications. It is normal to see
fluctuations at this point on the CommLink II. The average value should be close to the
acceptable range described below.
Values will vary upon initial powerup for about 10-15
seconds as the unit attempts to communicate.
Measurements
Network Loop
Acceptable Range
T - G (SHLD)
2.9 - 3.1 Volts DC
R - G (SHLD)
1.9 - 2.1 Volts DC
Action
Condition
Action
If voltages are too high or too low on either
side
1. Unplug the Network loop from the
CommLink II and Check for proper
loop voltages. If a problem exists,
disconnect each Zone Manager Network
Loop until the problem is isolated.
2. Check the CommLink II Driver chip.
Replace the driver chip if necessary.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...