Section 4
Auto-Zone Plus
4-20
Start-Up and Troubleshooting
1.3.10
Checking Zone Controller and CV Unit Drivers
Diagram
Meter Set To Read DC Volts
Note
These tests assume that the controller being checked is powered up.
Overview
This check is intended to determine if the Comm Driver chip on a controller is damaged.
Damage typically occurs when the communications loop is exposed to excessive voltage, as
may occur during installation, due to wiring errors. The driver chips are socketed on all
boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.
Almost all failures occur as a result of wiring related problems.
Measurements
Local Loop
Acceptable Range
T – SHLD
2.4 - 2.5 Volts DC
R – SHLD
2.4 - 2.5 Volts DC
Note
Minor variances may not indicate a problem if both tests indicate similar values.
Action
Condition
Action
If voltages are too high or too low on either
side
The controller has a damaged Comm
Driver chip.
Replace the driver chip.
See
"1.3.11Comm Driver Chip Replacement”.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...