Section 2
Auto-Zone
Plus
2-16
Design Guide
The Zone Controller requires the following electrical connections:
24VAC Supply Voltage............................................................................ 2 Conductors
Communications Loop........................................ 2 Conductor twisted pair with shield
( Belden #82760 or equivalent )
Room Temperature Sensor ...................................... 2 Conductors for standard sensors
3 Conductors for sensors with setpoint adjustment
Fan Terminal units / Auxiliary Heat...............2-4 Conductors see wiring diagrams for
(Optional) Aux. Relay board
Tip:
After making all electrical connections, it is suggested that all terminal blocks
on the Zone Controller be unplugged until you are ready to begin the checkout
procedure. This may help prevent damage if wiring errors occur elsewhere in the
system during installation or start-up. This is particularly important with the
Zone Controllers since an error on one unit may prevent any of the others from
working until the problem is found and corrected.
Warning:
Polarity is very important when connecting power to the controllers!
The grounded side of the control transformer must be connected to
the terminal labeled GND on the Zone Controller. If a single
transformer is used to power more than one Zone Controller you must
connect GND-to-GND and 24VAC-to-24VAC on each zone
controller. Failure to observe polarity will result in damage to one or
more components in your system.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...