Auto-Zone Plus
Section 3
Programming
3-19
Zone Controller Force
Modes
As a means of troubleshooting the system, the System Manager can Force the Zone
Controller to drive its damper, or force its Heating or Fan relays ON, regardless of the
current operating mode. The following screens show the available force modes for a
Zone Controller.
Note:
Be sure to remove the force mode when you are finished, or normal
operations will not resume!
Min/Max Force Modes
Open/Close Force Modes
ZONE FORCE MODES
Force to MINIMUM 0
Force to MAXIMUM 0
[0=Normal 1=Force]
In
Pressure Dependent
boxes you can force the damper to the
Maximum or the Minimum programmed damper position. This
is a percentage value that the damper drives to and stops.
In
Pressure Independent
boxes you can force the zone to
maintain the Maximum or Minimum Airflow setpoints. The
damper doesn't actually stop, but continues to move, if
required, to maintain one of these limits.
If the
Force to Minimum
is selected, the current minimum
position or airflow being used is the controlling position. This
minimum is based on the vent, heat, cool or unoccupied mode
of operation.
ZONE FORCE MODES
Force Full Open 0
Force Full Close 0
[0=Normal 1=Force]
The
Force Full Open
and
Force Full Close
modes ignore the
Pressure Dependent or Independent style of box. If one of the
modes is selected, the damper either drives to its full open
position and stops, or to its fully closed position and stops.
There is no mechanism for forcing the heating OFF.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...