Section 3
Auto-Zone Plus
3-24
Programming
Zone Manager
Configuration
These configuration setpoints are normally entered only one time and then never
accessed again. This is why they occupy their own menu location, so the user is not
required to step through these during normal setpoint Read and Reset.
Note
On initial power up, the system must be configured before it can be
successfully operated.
Configuration Screen #1
Caution:
The zones should be consecutively addressed with no skipped address
locations. If you do skip an address, the Zone Manager will presume
there is a missing zone, and an alarm will occur.
ZONE POLLING RANGE
Last Zone Addr: 1
First Zone Addr: 1
Cooling Stages: 1
Heating Stages: 1
The Zone Manager needs to know the
address range of the
attached Zone Controllers to be polled
. The user enters the
addresses of the first and last zones here. If you are controlling
from Return Air Temperature instead of voting zones, input –1
for both the first and last address.
The
quantity of cooling and heating stages
are also entered on
this screen.
Minimum
Default
Maximum
Last Zone Addr
1
1
16
First Zone Addr
1
1
16
Cooling Stages
0
1
6
Heating Stages
0
1
6
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...