9  Troubleshooting

Fault

Possible cause

Remedy

1

Underfloor heating circuits do not heat up; pump not running

1.1

Temperature limiter (TL) is switching the control station 

pump off. 
Reason: TL setting is too low.

Set TL to approx. 10 K higher than the underfloor heating 

flow temperature.
Note the maximum permitted temperature for the 

underfloor heating! 
The switching difference of the TL is approx. 5 K.
The control station is ready to operate more quickly if 

the TL is removed briefly to cool down to its switching 

temperature.

1.2

TL is switching the control station pump off. 
Reason: The pump remains switched on despite closed 

underfloor heating circuits. The water inside the control 

station is being heated by waste heat from the pump. The 

TL switches the pump off when the maximum temperature 

is reached!

Remove TL from the control station and fit to supply heating 

circuit manifold. 
Use electrical control distributor with pump logic (relay). The 

pump logic ensures that the pump runs only if at least one 

underfloor heating circuit is open.

1.3

The pump is connected to a room thermostat or electrical 

control distributor. 
If all actuators are closed, the pump switches off. During a 

lengthy shutdown, the underfloor heating flow cools down. 

The controller therefore causes the 3-way mixer valve 

to open. Hot water is injected from the primary heating 

circuit. As a result, the control station heats up. When the 

maximum temperature of the TL is reached, the contact 

opens. The pump does not switch on again.

Remove TL from the control station and fit to supply heating 

circuit manifold. 

See 1.1

2

Underfloor heating flow temperature cannot be set to the required value or the feed temperature fluctuates 

significantly

2.1

Supply and return on the control station have been mixed 

up

Check that all connections on the control station are correct 

(see Section “Structure” on page 5)

2.2

The head / pumping level of the pump is set too low

Change the pump setting (see separate pump instruction 

manual).

2.3

The differential pressure of the primary pump is too high 

(>500mbar)

Change the pump setting (see separate pump instruction 

manual) or fit differential pressure controller.

2.4

The heating load is too high for the control station, i.e. heat 

consumption exceeds the nominal output of the control 

station. This condition can come about temporarily, for 

example, when heating up a “cold” floor.

Establish maximum heat requirement and compare with 

nominal output. The heating circuits may have to be shared 

with a second control station with a corresponding heating 

circuit distributor. 
If this is caused by heating up the underfloor heating for the 

first time, it may start working normally after the heating up 

phase (2 – 3 days). This is particularly likely in the case of 

operation at the upper nominal output limit. 

Summary of Contents for Isomix-HC

Page 1: ...n surface heating cooling systems Installation and Operating Manual translated from the original operating manual Issued 10 2018 Revision 1 Watts Industries Deutschland GmbH Godramsteiner Hauptstr 167 76829 Landau Germany Tel 49 0 6341 96560 wide wattswater com WattsWater de ...

Page 2: ...on about the installa tion and operating manual The plant operator is responsible for ensuring compliance with the local laws and regulations e g accident prevention regulations etc Incorrect operation or operating the Isomix outside the specifications invalidates all warranty claims This installation and operating manual is an integral part of the Isomix contains instructions and information abou...

Page 3: ...ol mixture as per VDI 2035 ÖNORM Austrian standard 5195 Weight Total weight net approx 4 72 kg Total weight gross approx 5 05 kg Connections to pipe network 1 male thread primary heat generator 1 fl secondary heat distribution Isomix 1 flat sealing Materials Fittings Brass CW617 N nickel plated Seals and O rings AFM34 2 and EPDM Plastics Impact resistant and temperature resistant Circulation pump ...

Page 4: ...grated HEATING COOLING controller in accordance with the external temperature by means of a selectable heating cooling curve The steepness of the curve can be selected in accordance with the conditions at the location further details can be found in the operating manual for the controller The Isomix HC can be used to operate a heating system that is set to the individual requirements of a home or ...

Page 5: ...ve read these operating instructions and understood the potential hazards associated with improper behavior Fitters commissioning engineers Fitters commissioning engineers are in a position to carry out work on the Isomix taking into consideration the applicable standards provisions regulations and laws and their technical training and technical knowledge and can detect and prevent potential hazar...

Page 6: ...g controller There is a non return valve between the primary feed and the return connection on the mixer valve which prevents a short circuit in the primary circuit 6 Installation and commissioning Electrical energy Risk of death from electric shock Work on parts carrying live voltage must be carried out by qualified electricians only Disconnect the power supply of the system and secure it to prev...

Page 7: ...rive Red Blue White CLOSE OPEN System diagram of heating elements and surface heating cooling system Separate heating and cooling generator Separate risers System diagram of heating elements and surface heating system One heat generator Shared riser System diagram of surface heating cooling system Separate heating and cooling generator System diagram of surface heating cooling system Reversible he...

Page 8: ...xer tap More detailed information on scalding protection can be found in DIN 1988 sheet 2 section 4 2 During installation it must be ensured that the cables from the pump and temperature limiter are not kinked The cables must not be under tension 1 Fit the control station to the manifold with the 1 nuts and associated seals The control station can be fitted on the right or left of the manifold by ...

Page 9: ...a Heating circuits are closed 6 Open both fill and drain valves and fill the manifold and control station until water comes out of the fill and drain valve on the supply 7 Close both fill and drain valves 8 To fill and flush the heating circuits connect the filling hose to the supply fill and drain valve 6 9a and the emptying hose to the return fill and drain valve 6 9b 9 Open the heating circuit ...

Page 10: ... Use in combination with Watts Heat Interface Unit HIU 2 For use in combination with the HIU 2 Heat Interface Unit the Isomix HC must be converted overhead and the eccentric rotated 1 Release nut A A 2 Rotate eccentric B C B B Eccentric C Position of the contact thermostat ...

Page 11: ...ISOMIX HC IM DE W DE 10 2018 Rev1_enUS Art No 10070436 11 EN ENGLISH 7 Pressure loss curve Pressure loss Isomix floor control unit Pressure loss mbar Flow rate L h ...

Page 12: ...d 2 Functional check Check that settings and operating and performance parameters are set correctly Check flow noise during operation Ask users if there are any noticeable problems 3 Action to be taken following maintenance work Check that all screw fittings that were unscrewed have been retightened and retighten if necessary Remove all tools materials and other equipment used from the working are...

Page 13: ...ore causes the 3 way mixer valve to open Hot water is injected from the primary heating circuit As a result the control station heats up When the maximum temperature of the TL is reached the contact opens The pump does not switch on again Remove TL from the control station and fit to supply heating circuit manifold See 1 1 2 Underfloor heating flow temperature cannot be set to the required value o...

Page 14: ... materials 4 Dispose of the assemblies and components in accordance with local laws and regulations or take them to be recycled 11 1Return to the manufacturer Get in contact with the manufacturer if you would like to return the Isomix or parts of it 11 2 Notification of administrative bodies and the manufacturer Inform the manufacturer of decommissioning and disposal of the Isomix for statistical ...

Reviews: