5

CONTROL VALVE FUNCTIONS

This glass filled Noryl fully automatic control valve is designed
as the primary control center to direct and regulate all cycles of
a water softener. The control valve can be set to regenerate on
demand (consumption of a predetermined amount of water)
and/or as a time clock (passage of a particular number of days).

The control valve is compatible with a variety of regenerants
andresin cleaners. The control valve is capable of routing the
flow, of water in the necessary paths to regenerate or backwash
water treatment systems. The injector regulates the flow of brine
or other regenerants. The control valve regulates the flow rates
for backwashing rinsing and the replenishing of treated water into
a regenerant tank.

The control valve is designed to deliver high service (27 gpm @
15 psig) and backwash (27 gpm @ 25 psig) flow rates when the
bypass has straight fittings. The control valve uses no traditional
fasteners (e.g. screws), instead clips, threaded caps and nuts
and snap type latches are used. Caps and nuts only need to be
firmly hand tightened because radial seals are used. Tools
required to service the valve include one small blade screwdriv-
er, one large blade screwdriver, pliers and a pair of hands. A
plastic wrench is available which eliminates the need for screw-
drivers and pliers. Disassembly for servicing takes much less
time than comparable products currently on the market.

The transformer power pack comes with a 15-foot power cord
and is designed for use with the control valve. The transformer
power pack is for dry location use only. The control valve remem-
bers all settings for two hours if the power goes out. After two
hours the only item that needs to be reset is the time of day, all
other values are permanently stored in the nonvolatile memory.
The control valve does not need batteries.

When the control valve is used as a down flow softener, two
backwashes always occur. The softener will start regenerant
prefill before regeneration, the prefill starts two hours before the
regeneration time set. During the 2-hour period in which the brine
is being made, treated (softened) water is still available. For
example:regeneration time = 2:00 am, prefill option selected,
downflow softener. Fill occurs at 12:00 a.m., start of backwash
cycle occurs at 2:00 a.m.

The softener will adjust the backwash and rinse cycles automat-
ically 

when the

 salt dosage

 is changed 

. Backwashes can

be set to be NORMAL or LONGER. The option selected will
apply to all backwashes. Tables 4 and 5 show the length of the
cycles when the valve is set up as a softener.

REGENERATION STEPS AND PURPOSE:

Brine fill –

Brine tank is filled to dissolve salt for next

regeneration.

Backwash –

Flow through the resin bed is reversed.

Water flows upward expanding and agitating the resin bed.

Brine in –

Brine is educted from the brine tank and pass-

es through the resin bed in a downward flow, thus remov-
ing calcium and magnesium that has accumulated on the
resin beads and is flush to drain.

Backwash –

A second backwash is performed

Rinse –

The resin is now flushed downward at a set 

flow rate.

 This resettles the bed and rinses out any

remaining 

brine

 left in the resin bed.

Service – 

Softener goes back into service and ready to

soften water.

EXCHANGE CAPACITY DATA

20,000 grain approx. per cu. Ft.
6 lbs. salt-sodium chloride

25,000 grain approx. per cu. Ft.
8 lbs. salt-sodium chloride

30,000 grain approx. per cu. Ft.
15 lbs. salt-sodium chloride

Note:

To convert parts per million (PPM) or milligrams per

liter (mpl) to grains divide by 17.1

Example:

Water hardness of 250 PPM

(250 PPM divided by 17.1 PPM/gr.) equals 14.6 gr.

It is recommended that a good grade of solar or pellet salt
be used.

One-gallon water will dissolve approximately 3.0 lbs. of salt

One gallon of saturated brine weighs 10.74 lbs.

Control Valve Function and Cycles of Operation

Summary of Contents for M3011-W100SM

Page 1: ...OPERATING MANUAL WATER CONDITIONER with WM100SM valve WATER QUALITY CONDITIONING PRODUCTS...

Page 2: ...tting Assemblies 31 Bypass Valve 32 Flow Diagrams Service and Backwash 33 Flow Diagrams Downflow and Upflow 34 Flow Diagrams Rinse and Fill 35 WS1 Wrench 36 System Troubleshooting 37 38 Valve Troubles...

Page 3: ...ture often called ionized impurities which means they have an electrical charge The ion exchange process is based on the fact that like charges repel one another and unlike charges attract Calcium and...

Page 4: ...et b 3 4 1 PVC solvent weld fitting c 1 straight brass sweat fitting d 3 4 straight brass sweat fitting Distributor Tube Opening 1 05 Diameter 3 4 U S PVC Pipe Size Tank Thread 2 1 2 8 NPSM Control Va...

Page 5: ...does not need batteries When the control valve is used as a down flow softener two backwashes always occur The softener will start regenerant prefill before regeneration the prefill starts two hours b...

Page 6: ...k over flow to drain This is a gravity drain designed to divert brine to the drain in the event of a malfunction which would cause overflow of the brine tank Be sure inlet outlet isolating valves are...

Page 7: ...ling sweat copper follow state and federal codes by using a lead free solder and flux Use a joint compound to seal threaded pipe Some homes use the cold water pipes for an elec trical ground metal onl...

Page 8: ...nuts on installation fittings Hand tighten only Split ring retainer design holds the nut on and allows load to be spread over the entire nut surface area reducing the chance for leakage The split rin...

Page 9: ...Mode Figure 13 Bypass Mode Figure 14 Bypass Mode Figure 9 Brine Draw Connection STEP 5 Start up Place the bypass valve in the bypass position or mode see figures 12 14 below Open the main water supply...

Page 10: ...y reaches zero 2 Pressing and holding the REGEN button for approximately 3 seconds will immediately start the regeneration The user cannot cancel this request except by resetting the control by pressi...

Page 11: ...isplays is always the current time of day The second display is one of the following days remaining or gallons remaining Days remaining are the number of days left before the system goes through a reg...

Page 12: ...s may require periodic disinfecting Components The control valve consists of the following components 1 Drive Assembly 2 Drive Cap Assembly Main Piston and Regenerant Piston 3 Spacer Stack Assembly 4...

Page 13: ...es the velocity of the water cre ating a zone of negative pressure that draws in the concentrated liquid regenerant such as sodium chloride brine potassium permanganate sodium hydroxide hydrochloric a...

Page 14: ...orts etc The installation fitting assemblies are sold in pairs and consist of two fittings two nuts two split rings and two o rings The installation fitting assemblies and the bypass valve are sold se...

Page 15: ...te Lift up and outward on the drive bracket to disengage the notches To reassemble seat the bottom of the drive bracket so the notches are engaged at the bottom of the drive back plate Push the top of...

Page 16: ...assembly Reattach the regenerant piston if needed to the main piston Do not lubricate the piston rod main piston or regenerant piston Lubricant will adversely affect the red or clear lip seals Reinser...

Page 17: ...plugs If no water meter wire is visible then a plug is installed not a water meter The water meter wire does not need to be removed from the PC board if the water meter is only being inspected and cl...

Page 18: ...Front Cover ASY 1 2 KC12V3107 01 W100SM Motor 1 3 KC12F3106 01 W100SM Drive Bracket 1 Spring Clip 4 KC12V3108 W100SM PC Board 1 5 KC12V3110 W100SM Drive Gear 12x36 3 6 KC12V3109 W100SM Drive Gear Cove...

Page 19: ...ng No Order No Description Qty 1 KC12V3176 Injector Cap 1 2 KC12V3152 O ring 135 1 3 KC12V3177 Injector Screen 1 4 KC12V3010 12 W100SM Injector ASY Z Plug 1 5 KC12V3010 10 W100SM Injector ASY D Red 1...

Page 20: ...etainer ASY 1 8 KC12V3182 W100SM RFC 1 Assembly includes WS1 RFC This part is required for backwash only systems DRAIN LINE 3 4 Drawing No Order No Description Qty 1 KC12H4615 Elbow Locking Clip 1 2 K...

Page 21: ...0SM Split Ring 2 3 KC12V3105 O ring 215 2 4 KC12V3149 W100SM Fitting 1 PVC Male NPT Elbow 2 Drawing No Order No Description Qty 1 KC12V3151 W100SM Nut 1 Quick Connect 2 2 KC12V3150 W100SM Split Ring 2...

Page 22: ...10 KC12V3156 O ring 214 2 Not Shown Order No KC12 V3191 01 Description WS100sm Bypass Vertical Adapter Assembly Order No Description Qty KC12V3151 W100SM Nut 1 Quick Connect 1 KC12V3150 W100SM Split R...

Page 23: ...23 DRAWING AND PART NUMBERS flow diagram service flow diagram rinse flow diagram backwash flow diagram fill flow diagram downflow brine...

Page 24: ...nk is required F Leak at distributor tube F Make sure distributor tube is not cracked Check O Ring and tube pilot G Internal valve leaking G Replace seals and spacers and or piston 4 Unit used too muc...

Page 25: ...rol leak E Change seals spacers and piston assembly 10 Control cycles continuously A Broken or shorted switch A Determine if switch or timer is faulty and replace it or replace complete power head 11...

Page 26: ...source Jack black wire and plug back in to reset control valve b Foreign matter is lodged in control b Check piston and spacer stack valve assembly for foreign matter c High drive forces on piston c...

Page 27: ...ve gear or drive cap assembly d Defective PC board d Replace PC board a By pass valve in bypass position a Put control valve in service position b Meter connection disconnected b Connect meter to PC b...

Page 28: ...Manufactured by Watts Water Quality Conditioning Products 13700 Highway 90 W San Antonio TX USA FORM 0500 200 P N XOSW100SM DISTRIBUTED BY...

Reviews: