Installation, Maintenance, and Repair Manual
Series 009 and LF009
Series 009-FS and LF009-FS
Reduced Pressure Zone Assemblies
Size:
1
⁄
4
" – 3"
RP/IS-009/009-FS
Testing
For field testing procedure, refer to Watts installation sheets
IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D at watts.com.
For other repair kits and service parts, refer to the Backflow
Prevention Products Repair Kits & Service Parts price list PL-RP-
BPD at watts.com.
For technical assistance, contact your local Watts representative.
NOTICE
For Australia and New Zealand, line strainers should be installed
between the upstream shutoff valve and the inlet of the backflow
preventer.
Local building or plumbing codes may require modifications to the
information provided. You are required to consult the local building
and plumbing codes prior to installation. If this information is not
consistent with local building or plumbing codes, the local codes
should be followed.
Need for Periodic Inspection/Maintenance:
This product must
be tested periodically in compliance with local codes, but at least
once per year or more as service conditions warrant.
If installed on a fire suppression system, all mechanical checks,
such as alarms and backflow preventers, should be flow tested and
inspected in accordance with NFPA 13 and/or NFPA 25.
Corrosive water conditions and/or unauthorized adjustments or
repair could render the product ineffective for the service intended.
Regular checking and cleaning of the product’s internal components
helps assure maximum life and proper product function.
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information
can result in death, serious personal injury, property
damage, or damage to the equipment.
Keep this Manual for future reference.
Installation Instructions
Indoors
For indoor installations, the assembly needs to be easily accessible
to facilitate testing and servicing. If it is lo cat ed in a line close to a
wall, be sure the test cocks are easily accessible. A drain line and
air gap should be piped from the relief valve connection as shown
in Figure 1. This is where evidence of discharge is clearly visible,
signaling the need to protect against water damage. Therefore,
never install the assembly in concealed locations. (For more infor-
mation, download the ES-AG/EL/TC specification at watts.com.)
Figure 1
Air Gap
Main
Strainer
Meter
2
1
⁄
2
" – 3"
12"
Series 009-FS and LF009-FS assemblies of sizes ½" to 2" are
equipped with an integrated flood sensor that, when activated, trig-
gers notification of potential flood events from excessive relief valve
discharges. An add-on sensor connection kit is required to imple-
ment activation so that the alert system can be used with building
management systems or cellular communication. A retrofit sensor
connection kit is available for existing installations. See “Add-on and
Retrofit Sensor Connection Kits,” on pages 6 and 7, for the all
qualifying series models and valve sizes.
LF009M2-QT-FS