AERCO ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX B: AERCO Equipment Monitor and Control Point Definitions
OMM-0107_0B
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
45
of
108
GF-150
Ph.: 800-526-0288
03/07/2017
Appendix B: AERCO Equipment Monitor and Control Point
Definitions
Definitions of the monitor and control points associated with the AERCO Equipment
Configurations are provided in the tables below.
Appendix B-1:
AERCO C-More & ACS/BMS II/BMS Point Definitions
Point Name
BAS Modbus
Data Address
GF-108, GF-
124, GF-114
Point Name
Reg.
Type
Modbus Data
Address
(Hex/Dec.)
Units (Range)
C-More Boiler
Fire Rate Out
30009
Fire Rate Out
Input
0x0008 / 8
% (0 to 100)
Active Setpoint
30017
Active Set Point
Input
0x0010 / 16
deg F (40 to 220)
Net Remote Setpt
40001
Net Remote Set
Point
Holding
0x0000 / 0
deg F (40 to 220)
*Net Direct Drive
40002
Net Direct Drive
Holding
0x0001 / 1
% (0 to 100)
Fire Rate In
30018
Fire Rate In
Input
0x0011 / 17
% (0 to 100)
Outlet Temp
30003
Outlet Temp
Input
0x0002 / 2
deg F (30 to 245)
Display Code
30001
Default Message
Display Code
Input
0x0000 / 0
Enum (1 to 48)
See Appendix F
Unit Status
30002
Unit Status
Input
0x0001 / 1
Enum (0 to 5)
0 = Disabled
1 = Standby
2 = Manual Operation
3 = Remote Operation
4 = Auto Operation
5 = Fault
Run Cycles
30012-30013
Run Cycles
Input
0x000B - 0x000C /
11 - 12
(0 to 999,999)
Run Hours
30014-30015
Run Hours
Input
0x000D - 0x000E /
13 - 14
(0 to 999,999)
Oxygen
30010
O2 Level
Input
0x0009 / 9
% (0 to 25)
Exhaust Temp
30007
Exhaust Temp
Input
0x0006 / 6
Deg F (50 to 550)
* Where available in special profiles
ACS/BMS II/BMS
Fire Rate Out
30005
Fire Rate Out
Input
0x0004 / 4
% (0 to 100)
Header Set Temp
30006
Header Set
Temperature
Input
0x0005 / 5
°F (40 to 220)
Net Header Set Temp
40005
Net Header Set
Temp
Holding
0x0004 / 4
°F (40 to 220)
Header Temp
30002
Header
Temperature
Input
0x0001 / 1
°F (40 to 220)
Outside Air Temp
30003
Outside Air
Temperature
Input
0x0002 / 2
°F (-60 to 120)