AERCO ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX B: AERCO Equipment Monitor and Control Point Definitions
OMM-0107_0B
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
51
of
108
GF-150
Ph.: 800-526-0288
03/07/2017
Appendix B-4: AERCO WHM and BST Point Definitions
Point Name
BAS
Modbus
Data
Address
GF-108, GF-124, GF-114
Point Name
Reg.
Type
Modbus
Data
Address
(Dec.)
Units (Range)
Fault Code
3xx02
SMD_BAS_IP_HTR_(xx-2)_[2]
Input
xx01
Fault codes 0-74 matching the C-
More fault codes.
Outlet Temperature
3xx03
SMD_BAS_IP_HTR_(xx-2)_[3]
Input
xx02
°F (30 to 245)
FFWD Temperature
3xx04
SMD_BAS_IP_HTR_(xx-2)_[4]
Input
xx03
°F (30 to 245)
Inlet Temperature
3xx05
SMD_BAS_IP_HTR_(xx-2)_[5]
Input
xx04
°F (30 to 245)
Exhaust Temperature
3xx06
SMD_BAS_IP_HTR_(xx-2)_[6]
Input
xx05
°F (50 to 550)
Inlet Air Temperature
3xx07
SMD_BAS_IP_HTR_(xx-2)_[7]
Input
xx06
°F (-70 to 245)
Flame Strength
3xx08
SMD_BAS_IP_HTR_(xx-2)_[8]
Input
xx07
% (0 to 100)
Fire Rate IN
3xx09
SMD_BAS_IP_HTR_(xx-2)_[9]
Input
xx08
% (0 to 100)
Fire Rate OUT
3xx10
SMD_BAS_IP_HTR_(xx-2)_[10]
Input
xx09
% (0 to 100)
Unit Type
3xx11
SMD_BAS_IP_HTR_(xx-2)_[11]
Input
xx10
Enum List (0 to 5 or 8) (see note)
Unit Size
3xx12
SMD_BAS_IP_HTR_(xx-2)_[12]
Input
xx11
Enum List (0 to 21) (see note)
Valve State
3xx13
SMD_BAS_IP_HTR_(xx-2)_[13]
Input
xx12
0 = Closed , 1 = Open
Net Remote Setpoint
3xx14
SMD_BAS_IP_HTR_(xx-2)_[14]
Input
xx13
°F (40 to 200)
Run Cycles Upper 16 bits
3xx15
SMD_BAS_IP_HTR_(xx-2)_[15]
Input
xx14
0 to 65535 (see note)
Run Cycles Lower 16 bits
3xx16
SMD_BAS_IP_HTR_(xx-2)_[16]
Input
xx15
0 to 65535 (see note)
Run Hours Upper 16 bits
3xx17
SMD_BAS_IP_HTR_(xx-2)_[17]
Input
xx16
0 to 65535 (see note)
Run Hours Lower 16 bits
3xx18
SMD_BAS_IP_HTR_(xx-2)_[18]
Input
xx17
0 to 65535 (see note)
Oxygen Level
3xx19
SMD_BAS_IP_HTR_(xx-2)_[19]
Input
xx18
% (0 to 25)
IMPORTANT
For WHM and BST, use the SSD profiles.
NOTE
For WHM Heater or BST Boiler
#1, ‘xx’ = 03
#2, ‘xx’ = 04
#3, ‘xx’ = 05
#4, ‘xx’ = 06
#5, ‘xx’ = 07
#6, ‘xx’ = 08
#7, ‘xx’ = 09
#8, ‘xx’ = 10
Time
Time is expressed in minutes since midnight. For example, 360 equals 6 AM.
Run Cycles and Run Hours
Example:
Run Cycles = Run Cycles Upper 16 bits * 65536 + Run Cycles Lower 16 bits
Run Hours = Run Hours Upper 16 bits * 65536 + Run Hours Lower 16 bits