APPENDIX C: AERCO Equipment Point Mappings
Appendix C-1: AM Mngr Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus TCP/IP and
LonWorks
Appendix C-1:
AM Mngr Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus TCP/IP and LonWorks
Name / Point Name
BACnet
Object
Type
BACnet
Object
ID
N2
Data
Type
N2 Point
Address
Lon Name
Lon SNVT
Modbus
Address
Modbus Units
AV
1
AO
1
nvi/nvoModUnits_XXX
SNVT_count_f
40101
Device Type
AI
2
AI
2
nvoDevType_XXX
SNVT_count_f
40102
State
AI
3
AI
3
nvoState_XXX
SNVT_count_f
40103
Status
AI
4
AI
4
nvoStatus_XXX
SNVT_count_f
40104
Error Code
AI
5
AI
5
nvoErrCode_XXX
SNVT_count_f
40105
Warning Code
AI
6
AI
6
nvoWarnCode_XXX
SNVT_count_f
40106
Boiler CH SP
AV
7
AO
7
nvi/nvoBlrCHSP_XXX
SNVT_count_f
40107
Boiler DHW SP
AV
8
AO
8
nvi/nvoBlrDHWSP_XXX
SNVT_count_f
40108
Boiler Operation
AV
9
AO
9
nvi/nvoBlrOp_XXX
SNVT_count_f
40109
DHW Type
AV
10
AO
10
nvi/nvoDHWType_XXX
SNVT_count_f
40110
CH Mode
AV
11
AO
11
nvi/nvoCHMode_XXX
SNVT_count_f
40111
DHW Mode
AV
12
AO
12
nvi/nvoDHWMode_XXX
SNVT_count_f
40112
Supply Temp
AI
13
AI
13
nvoSupTmp_XXX
SNVT_count_f
40113
Return Temp
AI
14
AI
14
nvoRetTmp_XXX
SNVT_count_f
40114
DHW Temp
AI
15
AI
15
nvoDHWTmp_XXX
SNVT_count_f
40115
Flue Gas Temp
AI
16
AI
16
nvoFluGasTmp_XXX
SNVT_count_f
40116
Heat Exchanger Temp
AI
17
AI
17
nvoHtExcTmp_XXX
SNVT_count_f
40117
Firing Rate
AI
18
AI
18
nvoFirRate_XXX
SNVT_lev_percent
40118
Min Firing Rate
AI
19
AI
19
nvoMinFirRat_XXX
SNVT_lev_percent
40119
Flame Current
AI
20
AI
20
nvoFlmCrnt_XXX
SNVT_count_f
40120
Water Pressure
AI
21
AI
21
nvoWtrPrs_XXX
SNVT_count_f
40121
Analog in
AI
22
AI
22
nvoAnalogin_XXX
SNVT_count_f
40122
Analog out
AI
23
AI
23
nvoAnalogout_XXX
SNVT_count_f
40123