AERCO ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: Eight C-More Boilers/Heaters and BST/WHM Master
Page
70
of
108
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0107_0B
03/07/2017
Ph.: 800-526-0288
GF-150
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon
SNVT
Lon
Direction
Modbus
Address
4
Inlet Temp
SMD_BAS_IP_HTR_04_[5]
AV:605
Data Float
111
nvoHTR_04_6 inc count (9)
Output (non-polled)
30605
4
Exhaust Temp
SMD_BAS_IP_HTR_04_[6]
AV:606
Data Float
112
nvoHTR_04_7 inc count (9)
Output (non-polled)
30606
4
Air Temp
SMD_BAS_IP_HTR_04_[7]
AV:607
Data Float
113
nvoHTR_04_8 inc count (9)
Output (non-polled)
30607
4
Flame Strength
SMD_BAS_IP_HTR_04_[8]
AV:608
Data Float
114
nvoHTR_04_9 inc count (9)
Output (non-polled)
30608
4
Fire Rate In
SMD_BAS_IP_HTR_04_[9]
AV:609
Data Float
115
nvoHTR_04_10 inc count (9)
Output (non-polled)
30609
4
Fire Rate Out
SMD_BAS_IP_HTR_04_[10]
AV:610
Data Float
116
nvoHTR_04_11 inc count (9)
Output (non-polled)
30610
4
Unit Type
SMD_BAS_IP_HTR_04_[11]
AV:611
Data Float
117
nvoHTR_04_12 inc count (9)
Output (non-polled)
30611
4
Unit Size
SMD_BAS_IP_HTR_04_[12]
AV:612
Data Float
118
nvoHTR_04_13 inc count (9)
Output (non-polled)
30612
4
Value State
SMD_BAS_IP_HTR_04_[13]
AV:613
Data Float
119
nvoHTR_04_14 inc count (9)
Output (non-polled)
30613
4
Net Remote Setpt
SMD_BAS_IP_HTR_04_[14]
AV:614
Data Float
120
nvoHTR_04_15 inc count (9)
Output (non-polled)
30614
4
Run Cycles Upper
SMD_BAS_IP_HTR_04_[15]
AV:615
Data Float
121
nvoHTR_04_16 inc count (9)
Output (non-polled)
30615
4
Run Cycles Lower
SMD_BAS_IP_HTR_04_[16]
AV:616
Data Float
122
nvoHTR_04_17 inc count (9)
Output (non-polled)
30616
4
Run Hours Upper
SMD_BAS_IP_HTR_04_[17]
AV:617
Data Float
123
nvoHTR_04_18 inc count (9)
Output (non-polled)
30617
4
Run Hours Lower
SMD_BAS_IP_HTR_04_[18]
AV:618
Data Float
124
nvoHTR_04_19 inc count (9)
Output (non-polled)
30618
4
Oxygen Level
SMD_BAS_IP_HTR_04_[19]
AV:619
Data Float
125
nvoHTR_04_20 inc count (9)
Output (non-polled)
30619
Blr Addr 5
5
Comm Address
SMD_BAS_IP_HTR_05_[0]
AV:700
Data Float
126
nvoHTR_05_1 inc count (9)
Output (non-polled)
30700
5
Unit Status
SMD_BAS_IP_HTR_05_[1]
AV:701
Data Float
127
nvoHTR_05_2 inc count (9)
Output (non-polled)
30701
5
Fault Code
SMD_BAS_IP_HTR_05_[2]
AV:702
Data Float
128
nvoHTR_05_3 inc count (9)
Output (non-polled)
30702
5
Outlet Temp
SMD_BAS_IP_HTR_05_[3]
AV:703
Data Float
129
nvoHTR_05_4 inc count (9)
Output (non-polled)
30703
5
FFWD Temp
SMD_BAS_IP_HTR_05_[4]
AV:704
Data Float
130
nvoHTR_05_5 inc count (9)
Output (non-polled)
30704
5
Inlet Temp
SMD_BAS_IP_HTR_05_[5]
AV:705
Data Float
131
nvoHTR_05_6 inc count (9)
Output (non-polled)
30705
5
Exhaust Temp
SMD_BAS_IP_HTR_05_[6]
AV:706
Data Float
132
nvoHTR_05_7 inc count (9)
Output (non-polled)
30706
5
Air Temp
SMD_BAS_IP_HTR_05_[7]
AV:707
Data Float
133
nvoHTR_05_8 inc count (9)
Output (non-polled)
30707