AERCO ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: Eight C-More Boilers/Heaters and BST/WHM Master
OMM-0107_0B
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
75
of
108
GF-150
Ph.: 800-526-0288
03/07/2017
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon
SNVT
Lon
Direction
Modbus
Address
247
Percent Output
SMD_BAS_IP_OpVal_[12]
AV:112
Data Float
18
nvoOpVal_13
inc count (9)
Output (non-polled)
30112
247
Number of Units
Firing
SMD_BAS_IP_OpVal_[13]
AV:113
Data Float
19
nvoOpVal_14
inc count (9)
Output (non-polled)
30113
247
Master Active
Setpoint
SMD_BAS_IP_OpVal_[14]
AV:114
Data Float
20
nvoOpVal_15
inc count (9)
Output (non-polled)
30114
247
Next Turn-On
Percent
SMD_BAS_IP_OpVal_[15]
AV:115
Data Float
21
nvoOpVal_16
inc count (9)
Output (non-polled)
30115
247
Header High Limit
SMD_BAS_IP_OpVal_[16]
AV:116
Data Float
22
nvoOpVal_17
inc count (9)
Output (non-polled)
30116
247
Header Low Limit
SMD_BAS_IP_OpVal_[17]
AV:117
Data Float
23
nvoOpVal_18
inc count (9)
Output (non-polled)
30117
247
Header Temp High
Limit
SMD_BAS_IP_OpVal_[18]
AV:118
Data Float
24
nvoOpVal_19
inc count (9)
Output (non-polled)
30118
247
Header Setpoint
Mode
SMD_BAS_IP_OpVal_[19]
AV:119
Data Float
25
nvoOpVal_20
inc count (9)
Output (non-polled)
30119
Write Master Operating Values
247
Setpt
SMD_BAS_IP_CtrlVal_[0]
AV:200
Data Float
26
nvoCtrlVal_1 inc count (9)
Input (non-polling)
40200
247
Setback Setpt
SMD_BAS_IP_CtrlVal_[1]
AV:201
Data Float
27
nvoCtrlVal_2 inc count (9)
Input (non-polling)
40201
247
Setback Start
SMD_BAS_IP_CtrlVal_[2]
AV:202
Data Float
28
nvoCtrlVal_3 inc count (9)
Input (non-polling)
40202
247
Setback End
SMD_BAS_IP_CtrlVal_[3]
AV:203
Data Float
29
nvoCtrlVal_4 inc count (9)
Input (non-polling)
40203
* NOTE
Writing a setpoint to WHM or BST is a two-step process. First write the setpoint to the “Write Setpoint” address. Next, write a
“1” to the “Write Control” address. This will cause the ProtoNode to send the setpoint to the master C-More. After the setpoint is
sent, this address value will change to “0” when read.