4
70608-70609-MOI-IT-W-ML-04-22-Rev.2 K0111S – Rev. C 04/2022
UK
Technical Specifications
Threaded connections:
Rp UNI EN 10226-1
Maximun inlet pressure:
0.5 bar
Filtration degree:
≤ 50 µm
Working temperature:
-20°C÷+80°C
Mechanical strength:
according to UNI-EN 13611 (group 1)
Materials:
body in aluminium; cover in galvanized steel; filter
element with long-life Viledon P15/500S panels with remark-
able dust absorption in according to UNI EN ISO 16890 speci-
fications; cage for filters in synthetic material; NBR cover o-ring.
Fuels:
gas of the following groups: manufactured gases (town
gas); natural gases (group H - methane); liquid petrol gas (lpg);
non aggressive gases.
Installation
This filter, by reason of its limited dimensions, is particularly
suitable for installation on boilers (fixed to wall or ground) and
water heaters (instant or storage models).
Check that the filter suits the proper use and that all technical
data are not exceeded.
Do not install the filter on plastered walls.
To install the filter use suitable tools and operate on the thread-
ing hubs.
Assemble the filter in such a way that the cover can be easily
removed for inspection or cleaning.
Ensure that the gas flow direction is that indicated on the filter.
It can be assembled both on horizontal and vertical piping.
Maintenance
Change the filter element when Δp between the pressure taps
connections exceeds 10 mbar; anyway it is recommended to
replace the filter element at least once a year.
To replace the filter element you need to:
1. cut off the gas flow by closing the cut off cock;
2. unscrew the screws and remove the cover;
3. remove the filter element and clean the filter housing
carefully;
4. replace the old filter element with a new one;
5. reassemble the filter cover ensuring that the guides
inside the cover are aligned with the filter element and
then tight the screws again;
6. check for any gas leak from the filter cover.
The descriptions and photographs contained in this product specification sheet are supplied by way of information only and are not binding.
Watts Industries reserves the right to carry out any technical and design improvements to its products without prior notice. Warranty: All sales
and contracts for sale are expressly conditioned on the buyer’s assent to Watts terms and conditions found on its website at www.wattswater.
eu. Watts hereby objects to any term, different from or additional to Watts terms, contained in any buyer communication in any form, unless
agreed to in a writing signed by an officer of Watts.
GAS FILTER FOR WALL BOILERS
MOD.
Tightening torque [Nm]
70608
3,5
70609
3,5
ALL INSTALLATION AND MAINTENANCE OPERATIONS
MUST BE CARRIED OUT SOLELY BY QUALIFIED
PERSONNEL.