APPENDIX B: STARTUP, STATUS AND FAULT MESSAGES
PR2: 04/22/13 Page
111
of
158
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
Operation and Maintenance Manual
OMM-0052_0E
GF-127
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
Table B-2: Fault Messages (Continued)
FAULT MESSAGE
FAULT DESCRIPTION
OUTDOOR TEMP
SENSOR FAULT
The temperature measured by the Outdoor Air Sensor is out
of range.
OUTLET TEMP
SENSOR FAULT
The temperature measured by the Outlet Sensor is out of
range:
•
OUTLET TEMPERATURE display = SHt Indicates sensor
is shorted
•
OUTLET TEMPERATURE display = OPn indicates sensor
is open-circuited
PRG SWTCH CLOSED
DURING IGNITION
The Purge Position Limit Switch on the Air/Fuel Valve closed
during ignition.
PRG SWTCH OPEN
DURING PURGE
The Purge Position Limit Switch on the Air/Fuel Valve
opened during purge.
REMOTE SETPT
SIGNAL FAULT
The Remote Setpoint signal is not present or is out of range.
RESIDUAL
FLAME
The Flame signal was seen for more than 60 seconds during
standby.
SSOV
SWITCH OPEN
The SSOV switch opened during standby.
SSOV FAULT
DURING PURGE
The SSOV switch opened during purge.
SSOV FAULT
DURING IGN
The SSOV switch closed or failed to open during ignition.
SSOV FAULT
DURING RUN
The SSOV switch closed for more than 15 seconds during
run.
SSOV RELAY
FAILURE
A failure has been detected in one of the relays that control
the SSOV.
STEPPER MOTOR
FAILURE
The Stepper Motor failed to move the Air/Fuel Valve to the
desired position.