Benchmark 750-3000 Installation & Startup Manual
SECTION 2
– INSTALLATION
OMM-115_D
•
GF-200
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 27 of
126
2.9.1 Gas Supply Specifications
The gas supply input specifications to the unit are as follows:
The maximum static pressure to the unit must not exceed the following:
TABLE 2-1: Maximum Static Gas Pressure
Model
Natural gas
Propane
BMK 750 - BMK 3000
14” W.C. (3.49 kPa)
14” W.C. (3.49 kPa)
Supply piping and pressure to the unit must be sufficient to provide the volume of gas while
maintaining gas pressure listed below while
operating at maximum capacity
:
TABLE 2-2: Minimum Gas Pressure Requirements
Model
Natural gas
Propane
BMK 750
4” W.C. (1.0 kPa)
7” W.C. (1.74 kPa)
BMK 1000
4” W.C. (1.0 kPa)
11” W.C. (2.74 kPa)
BMK 1500
4” W.C. (1.0 kPa)
4” W.C. (1.0 kPa)
BMK 2000
4” W.C. (1.0 kPa)
4” W.C. (1.0 kPa)
BMK 2500
4” W.C. (1.0 kPa)
4” W.C. (1.0 kPa)
BMK 3000
4” W.C. (1.0 kPa)
4” W.C. (1.0 kPa)
2.9.2 Manual Gas Shutoff Valve
A manual shut-off valve must be installed in the gas supply line upstream of the boiler as shown
in Figure 1-1.