Benchmark 5000-6000 Operation & Maintenance Manual
APPENDIX A: BOILER MENU DESCRIPTIONS
OMM-0118_B
•
GF-203
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 101 of 148
Temperature Channel Offset:
Items 43
– 48 embody the feature, which allow the user to field calibrate all six temperature
channels by entering an offset corresponding to the desired temperature channel.
43
– FFWD Temp Offset Range: -20 to + 20 (either ºF or °C)
44
– Exhst Tmp Ofset
Range: -20 to + 20 (either ºF or °C)
45
– Outdr Air Offset
Range: -20 to + 20 (either ºF or °C)
46
– Inlet Air Offset
Range: -20 to + 20 (either ºF or °C)
47
– Inlet Wtr Offset
Range: -20 to + 20 (either ºF or °C)
48
– Outlet Wtr Offset
Range: -20 to + 20 (either ºF or °C)
49
24 hr Max Cycles
Maximum cycles in 24 hour period.
50
24 hr Max Ovrtemp
Maximum over-temp in 24 hour period.
51
0-10v Out Test
Set the blower voltage at 0-10v for testing.
52
Spark Monitor
Enables or disables the Spark Monitor function, which displays the
AC current on the input of the Ignition Transformer.
53
Min Spark Amps
Allows the adjustment of the minimum spark current required at the
spark transformer input.
54
Max Spark Amps
Allows the adjustment of the maximum spark current required at
the spark transformer input.