Benchmark 5000-6000 Operation & Maintenance Manual
APPENDIX E: INDOOR/OUTDOOR RESET RATIO CHARTS
OMM-0118_B
•
GF-203
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 112 of 148
Header Temperature for a Building Reference Temperature = 65°F (18.3°C)
AIR TEMP
RESET RATIO
°F
°C
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
65
18.3
65
65
65
65
65
65
65
65
65
65
60
15.6
68
69
70
71
72
73
74
75
76
77
55
12.8
71
73
75
77
79
81
83
85
87
89
50
10.0
74
77
80
83
86
89
92
95
98
101
45
7.2
77
81
85
89
93
97
101
105
109
113
40
4.4
80
85
90
95
100
105
110
115
120
125
35
1.7
83
89
95
101
107
113
119
125
131
137
30
-1.1
86
93
100
107
114
121
128
135
142
149
25
-3.9
89
97
105
113
121
129
137
145
153
161
20
-6.7
92
101
110
119
128
137
146
155
164
173
15
-9.4
95
105
115
125
135
145
155
165
175
185
10
-12.2
98
109
120
131
142
153
164
175
186
197
5
-15.0
101
113
125
137
149
161
173
185
197
209
0
-17.8
104
117
130
143
156
169
182
195
208
-5
-20.6
107
121
135
149
163
177
191
205
219
-10
-23.3
110
125
140
155
170
185
200
215
-15
-26.1
113
129
145
161
177
193
209
-20
-28.9
116
133
150
167
201
218
Header Temperature for a Building Reference Temperature = 70°F (21.1°C)
AIR TEMP
RESET RATIO
°F
°C
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
70
21.1
70
70
70
70
70
70
70
70
70
70
65
18.3
73
74
75
76
77
78
79
80
81
82
60
15.6
76
78
80
82
84
86
88
90
92
94
55
12.8
79
82
85
88
91
94
97
100
103
106
50
10.0
82
86
90
94
98
102
106
110
114
118
45
7.2
85
90
95
100
105
110
115
120
125
130
40
4.4
88
94
100
106
112
118
124
130
136
142
35
1.7
91
98
105
112
119
126
133
140
147
154
30
-1.1
94
102
110
118
126
134
142
150
158
166
25
-3.9
97
106
115
124
133
142
151
160
169
178
20
-6.7
100
110
120
130
140
150
160
170
180
190
15
-9.4
103
114
125
136
147
158
169
180
191
202
10
-12.2
106
118
130
142
154
166
178
190
202
214
5
-15.0
109
122
135
148
161
174
187
200
213
0
-17.8
112
126
140
154
168
182
196
210
-5
-20.6
115
130
145
160
175
190
205
-10
-23.3
118
134
150
166
182
198
214
-15
-26.1
121
138
155
172
189
206
-20
-28.9
124
142
160
178
196
214