Benchmark 5000-6000 Operation & Maintenance Manual
SECTION 2: OPERATION
OMM-0118_B
•
GF-203
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 19 of 148
2.4 OPERATING Menu
The
Operating
menu displays a number of key operating parameters for the unit. All items in this
menu except
O2 Monitor
(item 15) are “Read-Only” and cannot be changed. This menu can be
accessed without entering a password.
A full description of each item appears in Appendix A-1.
TABLE 2-2: OPERATING Menu
MENU ITEM DISPLAY
AVAILABLE CHOICES OR LIMITS
Appears Only If
Enabled in:
Minimum
Maximum
1
Active Setpoint
40°F (4.4
°
C)
240°F (116
°
C)
2
Outlet Temp
30°F (-1.1
°
C)
240°F (116
°
C)
Configuration Menu
3
Inlet Temp
30°F (-1.1
°
C)
240°F (116
°
C)
4
Air Temp
-70°F (-56.7
°
C)
245°F (118
°
C)
5
Outdoor Temp
-70°F (-56.7
°
C)
130°F (54.4
°
C)
Configuration Menu
6
Valve Position In
0%
100%
7
Valve Position Out
0%
100%
Configuration Menu
8
FFWD Temp
30°F (-1.1°C)
240°F (115.6°C)
9
Exhaust Temp
Displays current exhaust temperature
10
Flame Strength
0%
100%
11
Min Flame Str
Not Used
12
O2 Monitor
Enable
Disable
13
Oxygen Level
0%
21%
O2 Monitor = Enabled
14
Ignition Time
0.00
10.00
15
SSOV Time to OPN
0.00
10.00
16
Air Pump Voltage
0.20 V
1.2 V
17
Run Cycles
0
999,999,999
18
Run Hours
0
999,999,999
19
Fault Log
0
19
20
Manual Valve Pos *
0
100
* NOTE
Manual Valve Pos
does not appear in this menu unless you push the
Auto/Man
button on
the C-More Controller
’s front face.