Benchmark 5000-6000 Operation & Maintenance Manual
SECTION 2: OPERATION
OMM-0118_B
•
GF-203
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 26 of 148
TABLE 2-7: BST Menu
MENU ITEM DISPLAY
AVAILABLE CHOICES OR LIMITS
DEFAULT
Minimum
Maximum
47
BST Setpt HI Limit
BST Setpt Lo Limit
220°F (104.4°C)
195°F (90.6°C)
48
BST Prop Band
1°F (-17.2°C)
120°F (48.9°C)
100°F (37.8°C)
49
BST Intgral Gain
0.00
2.00
0.50
50
BST Deriv Time
0.00 Min
2.00 Min
0.10 Min
51
BST Deadband Hi
0
25
1
52
BST Deadband Lo
0
25
1
53
Deadband En Time
0
120 Sec
30 Sec
54
BST FR Up Rate
1
120
20
55
BST Bldg Ref Tmp
40°F (4.4°C)
230°F (110°C)
70°F (21.1°C)
56
BST Reset Ratio
0.1
9.9
1.2
57
System Start Tmp
30°F (-1.1°C)
120°F (48.9°C)
60°F (15.6°C)
58 *BST COMM MENU*
Disabled
Enabled
Disabled
59
Comm Address
0
127
0
60
BST Min Addr
1
128
1
61
BST Max Addr
1
128
8
62
SSD Address
0
250
247
63
SSD Poll Control
0
1000
0
64
Err Threshold
1
9
5
65
SSD Temp Format
Degrees
Points
Degrees
66
BST Upld Timer
0
9999 sec
0