Benchmark 5000-6000 Operation & Maintenance Manual
SECTION 2: OPERATION
OMM-0118_B
•
GF-203
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 28 of 148
TABLE 2-8: Calibration Menu
MENU ITEM DISPLAY
AVAILABLE CHOICES OR LIMITS
DEFAULT
Minimum
Maximum
14
Exhst Module Temp
100 °F
500 °F
190 °F
15
Exhst Warn Temp
100 °F
500 °F
180 °F
16
Exhst Tmp VP Adj
0
10
5
17
Exhst Adj Rate
1
600
30
18
VP Change Rate
5
600
25
19
VP Up Rate
0.5
60.0
Depends on unit type/size
20
VP Down Rate
0.5
60.0
Depends on unit type/size
21
Purge Blwr Offst
-1.0
8.0
Depends on unit type/size
22
4-20mA Purge Pct
60%
100%
70%
23
PWM In Adj
-5.0%
5.0%
0.0%
24
Analog In Adj
-5.0%
5.0%
0.0%
25
Flow In Adj
-5.0%
5.0%
0.0%
26
Supply Gas Pressure In Adj
-5.0%
5.0%
0.0%
27
Gas Plate dp In Adj
-5.0%
5.0%
0.0%
28
mA Out Adj
-1.0 mA
1.0 mA
0.0 mA
29
A/F Sensitivity
1%
5%
2%
30
Power Reset
Automatic or Manual
Automatic
31
Water Temp Reset
Automatic or Manual
Automatic
32
Gas Press Reset
Automatic or Manual
Manual
33
Min Off Time
0 Min
15 Min
0 Min
34
Stop Level
0%
Start Level
16
35
Start Level
Stop Level
40%
20
36
Skip Range Cntr
10
95
40
37
Skip Range Span
0
3
0
38
Skip Speed
0.5
2.0
0.5
39
O2 Gain
0.500
1.500
1.024
40
O2 Offset
-24.0
+2.0
0
41
O2 Sensor
Enabled or Disabled
Depends on unit type/size
42
Cal Temp Sensors
Off or Start
Off
43
FFWD Temp Offset
-20
+20
0
44
Exhst Tmp Offset
-20
+20
0
45
Outdr Air Offset
-20
+20
0