Benchmark 5000-6000 Operation & Maintenance Manual
APPENDIX A: BOILER MENU DESCRIPTIONS
OMM-0118_B
•
GF-203
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 93 of 148
TABLE A-2: SETUP MENU ITEM DESCRIPTIONS
See Section 2-5 for a range of choices and the default values.
TABLE A-2: SETUP Menu Item Descriptions
MENU OPTIONS
DESCRIPTION
1
Password
Allows Level 1 or Level 2 password to be entered.
Entering the Level 1 Password (159) allows options in the
Setup
,
Configuration
and
Tuning
menus to be modified.
Entering the Level 2 Password (6817) allows options in the
Calibration and Diagnostics Menus to be changed or activated, in
addition to all Level 1 Menu options.
2
Language
Permits selection of the language of displayed messages. English is
the only option at this time.
3
Time
Displays time from 12:00 am to 11:59 pm.
4
Date
Displays dates from 01/01/00 to 12/31/99
5
Unit of Temp
Permits selection of temperature displays in degrees Fahrenheit (°F)
or degrees Celsius (°C).
6
Comm Address
For RS-485 communications. RS232 should have its own
(programmable) password.
7
Baud Rate
Allows communications Baud Rate to be set (2400 to 19.2K).
Default is 9600.
8
onAER Mode
Allows selection of either
Ethernet
or
SD Card
.
9
Min Upload Timer
Mandatory for AERCO onAER Remote Data Collection (ORDC).
This parameter enables ORDC and defines the minimum amount of
time between heartbeat data uploads in seconds. The COMM LED
will light during the upload.
10
Unit Alpha
Mandatory for AERCO onAER Remote Data Collection. This value
must match the first alpha digit on the Code Plate, e.g.,
G
-12-1234.
11
Unit Year
Mandatory for AERCO onAER Remote Data Collection. This value
must match the 2-digit year on the Code Plate, e.g., G-
12
-1234.
12
Unit Serial #
Mandatory for AERCO onAER. Remote Data Collection. This value
must match the 4-digit serial # on the Code Plate, e.g., G-12-
1234
.
13
Software Version
Identifies the current software version of the C-More Controller.