Benchmark 5000-6000 Operation & Maintenance Manual
APPENDIX A: BOILER MENU DESCRIPTIONS
OMM-0118_B
•
GF-203
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 94 of 148
TABLE A-3: CONFIGURATION MENU ITEM DESCRIPTIONS
See Section 2-6 for a range of choices and the default values.
The
Configuration
menu settings are Factory-Set in accordance with the requirements specified
with each individual order. No changes will be required under normal operating conditions.
TABLE A-3: CONFIGURATION Menu Item Descriptions
MENU OPTIONS
DESCRIPTION
1
Internal Setpoint
Allows internal setpoint to be set from Lo Temp Limit of 40°F to
Hi Temp Limit of 240°F (4.4°C to 115.6°C).
2
Unit Type
Can be one of the following: BMK Blr Std, BMK Blr Std Dual,
BMK Blr LN, BMK Blr LN Dual.
3
Unit Size
Sets unit size, depending on the Unit Type:
Benchmark
5000
– 5000 MBH (1465 kW)
Benchmark
6000
– 6000 MBH (1758 kW)
4
Fuel Type
Allows selection of Natural Gas or Propane.
5
Boiler Mode
Only available if Unit Type = Boiler.
Allows selection of:
Constant Setpoint, Remote Setpoint, Direct Drive,
Combination, or Outdoor Reset Mode.
6
Remote Signal
Only available if Mode = Remote Setpoint, Direct Drive or
Combination. Used to set the type of external signal which will
be used when operating in the Remote Setpoint, Direct Drive
or Combination Mode.
7
Outdoor Sensor
Allows outdoor sensor function to be set to Enabled or
Disabled.
8
Bldg Ref Temp
Only available if Boiler Mode =
Outdoor Reset
. Allows the
building reference temperature to be set when operating a
boiler in the Outdoor Reset Mode.
9
Reset Ratio
Only available if Boiler Mode =
Outdoor Reset
. Permits setting
of Reset Ratio when operating boiler in the Outdoor Reset
Mode.
10
System Start Tmp
Only if Outdoor Sensor =
Enabled
. This menu item allows the
system start temperature to be set.
11
Setpt Lo Limit
Used to set the
minimum
allowable setpoint, from 40°F (4.4
°C)
up to the Setpt Hi Limit.
12
Setpt Hi Limit
Used to set the
maximum
allowable setpoint, from the Setpt Lo
Limit up to 210°F (98.9
°C)
.
13
Temp Hi Limit
This is the maximum allowable outlet temperature, up to 210°F
(98.9
°C)
. Any temperature above this setting will turn off the
unit. The temperature must then drop 5°F (2.75
°C)
below this
setting to allow the unit to run.
14
Max Valve Position
Sets the maximum allowable valve position for the unit.
15
Pump Delay Timer
Specifies the amount of time, up to 30 minutes, to keep the
pump running after the unit turns off.