TABLE 10-1: Boiler Troubleshooting Procedures
Fault
Probable Causes
Corrective Action
2.
Defective SSOV Actuator.
2.
If gas supply pressure downstream of SSOV Actuator cannot be
lowered to the range specified in Table 4-1 (Natural Gas) or Table 4-
4 (Propane) in Section 4.4:
Combustion Calibration
of this
guide; the
SSOV Actuator may be defective.
3.
Defective
High Gas Pressure
switch.
3.
Remove the leads from the High Gas Pressure switch. Measure
continuity across the common (C) and normally closed (NC)
terminals with the unit not firing. Replace the switch if continuity
does not exist.
HIGH WATER
TEMP SWITCH
OPEN
1.
Faulty Water temperature switch.
1.
Test the temperature switch to insure it trips at its actual water
temperature setting.
2.
Incorrect PID settings.
2.
Check PID settings (
Advanced Setup
Performance
Temperature
Control
, first 3 items). If the settings have been
changed, record the current readings then reset to default values.
3.
Faulty shell temperature sensor.
3.
Using the resistance charts in Section 2 of the
Benchmark Platinum-
Edge: REFERENCE Manual
(GF-212) measure the resistance of
Shell sensor and BTU sensor at a known water temperature.
4.
Unit in
Manual
mode.
4.
If unit is in
Manual
mode, switch to
Auto
mode (
Diagnostic
Manual Run,
set
Manual Mode = Enabled
).
5.
Unit setpoint is greater than Over Temperature
switch setpoint.
5.
Check setpoint of unit and setpoint of Temperature switch; Ensure
that the temperature switch is set higher than the unit’s setpoint.
6.
System flow rate changes are occurring faster
than units can respond.
6.
If the system is a variable flow system, monitor system flow changes
to ensure that the rate of flow change is not faster than what the
units can respond to.
HIGH WATER
TEMPERATURE
1.
See HIGH WATER TEMPERATURE SWITCH
OPEN.
1.
See HIGH WATER TEMPERATURE SWITCH OPEN.
2.
Temp HI Limit setting is too low.
2.
Check Temp HI Limit setting.
IGN BOARD
COMM FAULT
1.
Communication fault has occurred between the
PMC board and Ignition/Stepper (IGST) board.
1.
Press
CLEAR
button and restart unit. If fault persists, contact
qualified Service Personnel.
2.
32 Pin Ribbon cable defective.
2.
Replace 32 Pin Ribbon cable.