Benchmark Platinum-Edge [ii]: Installation Manual
SECTION 2
– INSTALLATION
OMM-
136_E • GF
-210
•
12/13/2019
Technical Support
• (
800) 526-0288
• Mon
-Fri, 8 am - 5 pm EST Page 39 of 57
Connector Strip J6 Terminals
Pin # Name
Description
1
Remote Interlock Out
Connection to an auxiliary device interlock, such as louver open
feedback or flow sensor.
2
Remote Interlock Return
3
Delayed Interlock 1 Out
Connection to an auxiliary device interlock that requires a delay before
the plant starts firing.
4
Delayed Interlock 1 Return
5
Delayed Interlock 2 Out
Connection to an auxiliary device interlock that requires a delay before
the plant starts firing.
6
Delayed Interlock 2 Return
Connector Strip J7 Terminals
Pin # Name
Description
1
Spare 2 Relay N.O.
Connection to an auxiliary device enable/disable signal, such as:
•
System Pump
•
Summer Pump
•
Pump 2
•
Louver
•
Louver 2
•
Damper
•
Other
To assign/program its function, go to the Controller’s
Main Menu
→
Advanced Setup
→
Ancillary Devices
→
Relays
,
then set the
Relay
to
Spare 2 Relay
and the
Name
to one of the above devices.
2
Spare 2 Relay Com
3
DHW Pump Relay N.O.
Connection to a DHW Pump enable/disable signal.
4
DHW Pump Relay Com
5
V2/Spare 1 Relay N.O.
Connection to an auxiliary device enable/disable signal, such as:
•
Swing Valve 2
•
System Pump
•
Summer Pump
•
Pump 2
•
Louver
•
Louver 2
•
Damper
•
Other
To assign/program its function, go to the Controller’s
Main Menu
→
Advanced Setup
→
Ancillary Devices
→
Relays
,
then set the
Relay
to
V2/Spare 1 Relay
and the
Name
to one of the above
devices.
6
V2/Spare 1 Relay Com
7
Backup Relay N.O.
Connection to a reserve/backup boiler enable/disable signal.
8
Backup Relay Com
9
Swing Valve 1 Relay N.O.
Connection to a Swing Valve 1 enable/disable signal.
10
Swing Valve Relay Com
11
Fault Relay N.O.
Connection to a Fault/Remote Alarm enable/disable signal.
12
Fault Relay Com
13
Aux Relay N.O.
Connection to an auxiliary device enable/disable signal.
14
Aux Relay Com
Connector Strip J14 Terminals
Pin # Name
Description
1
BAS RS485 +
Connection to the building automation system (BAS) network (Modbus RTU,