Innovation Hot Water Hot Water Boiler User Manual
- INTERNATIONAL
APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS
Page
134
of
174
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0120_0A
11/15/2016
Phone: 800-526-0288
GF-128-I
Table A-5:
CALIBRATION MENU ITEM DESCRIPTIONS
See section 3-8 for a range of choices and the default values.
MENU LEVEL & OPTION
DESCRIPTION
22
Water Temp Reset
Allows the Water Temperature Reset function to be set to AUTO or
MANUAL.
23
Gas Press Reset
Allows the Gas Pressure Reset function to be set to AUTO or
MANUAL.
24
Min Off Time
Allows the minimum Off time to be set from 0 to 10 minutes.
25
Heatr Tuning Dsp
Allows Heater Tuning Display to be Enabled or Disabled.
26
Heatr Bkpt Dsp
Allows Heater Breakpoint Display to be Enabled or Disabled. When
Enabled, Breakpoints can be viewed and/or changed.
27
Stop Level
Allows the Stop Level to be set to a valve position ranging from 0% to
the presently set Start Level.
28
Start Level
Allows the Start Level to be set to a valve position ranging from the
presently set Stop Level to a maximum of 40%.
SKIP FEATURE:
Items 29 – 31 embody a feature that allows the user to define a Fire Zone the C-More will avoid. In
the rare instance when a unit emits an objectionable noise at a certain Fire Rate and no other remedy
solves the problem, a Fire Rate skip zone may be defined to command the C-More to Skip-Over the
defined Fire Rate.
29
– Skip Range CNTR
Defines the Center (Fire Rate) of the skip band.
30
– Skip Range Span
Defines the + and – band of the Skip Zone Size.
31
– Skip Speed
Defines the speed (Seconds/Fire Rate) at which the band will be
skipped.
O2 Settings
:
Items 32 – 34 allow calibration of oxygen readings.
32
– O2 Gain
Range = 0.1 to 1.5. (Unity Gain, No Mods)
33
– O2 Offset
Range = -3.0 to +3.0.
34
– O2 Sensor
Enables the O2 Sensor
35
Cal Temp Sensors
Allows calibration of the temperature sensor
Temperature Channel Offset:
Items 36 – 41 embody the feature, which allow the user to field calibrate all six temperature channels
by entering an offset corresponding to the desired temperature channel.
36
– FFWD Temp Offset
Range = ± 20 ºF (± 11.1 °C)
37
– Exhst Tmp Offset
Range = ± 20 ºF (± 11.1 °C)
38
– Outdr Air Offset
Range = ± 20 ºF (± 11.1 °C)
39
– Inlet Air Offset
Range = ± 20 ºF (± 11.1 °C)
40
– Inlet Wtr Offset
Range = ± 20 ºF (± 11.1 °C)