CHAPTER 2 – INSTALLATION
OMM-0120_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
23
of
174
GF-128-I
Phone: 800-526-0288
11/15/2016
--CAUTION -
Use PVC, stainless steel, aluminum or polypropylene for condensate drain
piping (Figure 2-7). DO NOT use carbon or copper components.
NOTE
Two different styles of condensate traps are currently in use. The functions
and connections provided are nearly identical however they look slightly
different.
LEFT SIDE VIEW
Figure 2-7. Sample Condensate Trap Installation
NOTE
As a general guideline, AERCO recommends use of its Condensate
Neutralizer Kit to raise the pH level of the condensate prior to drainage. At
a minimum, the installation must be designed in accordance with local
codes that specify acceptable pH limits. For more information, see
Technical Instruction Document TID-0029, Condensate Neutralization Kit
and TID-0074 Condensate Neutralization Tank.
Housekeeping pad should not extend under the condensate assembly
HOUSEKEEPING
SUPPOR
EXHAUST
MANIFOLD
CONDENSATE
TRAP
TO
FLOOR
DRAIN
3/4”
(1.91 cm)
NIPPLES
1”
(2.54 cm)
I.D. HOSE
& CLAMP
ADAPTER
WITH
INTERNAL