8
NOTICE
The ReliaGuard gas connector system has the following possible installation configurations
which all require the use of a restraining cable:
• Gas Line - Manual Shut-Off Valve - ReliaGuard - Appliance
• Gas Line - Manual Shut-Off Valve - ReliaGuard - Standard Snap™ - Appliance
• Gas Line - Manual Shut-Off Valve - SwivelGuard - ReliaGuard - Standard Snap - Appliance
• Gas Line - Manual Shut-Off Valve - ReliaGuard - SwivelGuard - Standard Snap - Appliance
• Gas Line - Manual Shut-Off Valve - SwivelGuard - ReliaGuard - SwivelGuard - Standard Snap - Appliance
• Gas Line - Manual Shut-Off Valve - Standard Snap - ReliaGuard - Appliance
• Gas Line - Manual Shut-Off Valve - Standard Snap - SwivelGuard - ReliaGuard - Appliance
• Gas Line - Manual Shut-Off Valve - Standard Snap - ReliaGuard - SwivelGuard - Appliance
• Gas Line - Manual Shut-Off Valve - Standard Snap - SwivelGuard - ReliaGuard - SwivelGuard - Appliance
NOTICE
Please carefully consider your installation configuration and identify the relevant steps for
installation before you begin your installation . Be sure that the gas connector to be used is
the right length and type for the location and appliance to be served . Only one gas connector
should be used per appliance .
Refer to the additional install instructions and warnings provided with the Dormont Standard
Snap QD, and Restraining Cable products .
NOTICE
In identifying the proper configuration for your installation, consideration should be given to
the location of the connection end points for the gas supply and the appliance . Note that the
location of the gas supply and appliance connection end points can vary greatly in each loca-
tion and for each appliance . Dormont rec-
ommends that the gas supply manifold be
located 30 to 42 inches from the floor . Any
pipe tees should be pointed in the down-
ward direction upon installation . To ensure
that the appliance can be moved as close
as possible to the wall for maximum aisle
space, the ReliaGuard should be installed so
that its two ends are offset to the side from
each other (+/- 3" offset is recommended)
and parallel (never perpendicular) to both the
wall and the appliance . See Figure A .
WARNING
!
Each appliance connected with a ReliaGuard gas connector MUST have its own approved
manual shutoff valve . If the appliance being connected does not yet have a manual shutoff
valve, then the gas must be shut off at the main manifold shutoff valve and an approved man-
ual shutoff valve MUST be installed . The main manifold shutoff valve also MUST be turned off
if a manual shutoff valve is being replaced or installed on the gas supply manifold .
Two 14" adjustable wrenches and a pipe wrench are recommended
as installation tools .
ReliaGuard Warnings and Configurations
W
A
L
L
EQUIPMENT
OFFSET
Figure A
Top-Down View