Installation and Operation
For New and Existing LFF113RFP ACV Installations
For convenience, new LFF113RFP ACVs are shipped with a
Solenoid prewired to the Relay Box. Retrofitting an existing
LFF113RFP requires an electrician to make that connection
manually. New and existing ACV systems both require wiring to
the Relay Box.
For Existing LFF113RFP Installations Only
1. After removing power from the circuit, disengage the wiring
from the main terminals inside existing Control Box:
• Terminals 1 and 2 (Flood Sensor)
• Terminals 3 and 4 (Solenoid)
• Terminals 5 and 6 (Remote Trip Indicator, if wired)
2. Remove the Control Box from the ACV or wall mount.
3. Replace the existing control box and mounting bracket with
the new Relay box and mounting bracket.
4. Using the cable from Solenoid, connect the Solenoid to the
Relay Box. Attach the cable to the terminals 5 and 6 in the
Relay Box. There is no polarity.
5. The Relay Box includes several spare terminals for your con-
venience to ease wiring requirements, such as building moni-
toring inputs or valve positioning.
For New and Existing LFF113RFP Installations
1. Using an electrical cable (not provided), connect terminals 3
and 4 in the Relay Box to 110VAC power.
2. Using a 300 V, 14-24 AWG cable (not provided), connect the
Relay Box to the Control Box. Attach one end of the cable
to terminals 7 and 8 in the Relay Box. Attach the other end
of the cable to the terminals labeled ACV in the Control Box.
Connect Terminal 7 to ACV+. Connect Terminal 8 to ACV-.
Solenoid Operation
The Solenoid is equipped with a Solenoid Bypass Valve (nor-
mally closed) which manually
closes the Main Valve when
engaged.
Opening the Solenoid Bypass
Valve pressurizes the Main
Valve cover as indicated by a
pressure gauge, closing the
Main Valve.
Closing the Solenoid Bypass
Valve and opening the Manual
Reset Ball Valve returns the
Main Valve to the full open
position.
The pressure gauge returns to
zero when the Main Valve is
fully open.
NOTE:
Manual Reset Ball Valve must be closed for normal oper-
ation.