The RoomResponse

TM

 signal adjusts the temperature of 

a modulating condensing boiler that accepts a 0-10 V(dc) 
or 4-20 mA input. It works by continually adjusting boiler 
water temperatures to the lowest possible value to meet 
comfort without wasting energy. This is done by monitoring 
each thermostat's on and off time pattern and determines 
the ideal water temperature for each zone. The control 
then chooses the highest water temperature requirement 
of all the thermostats and provides a 0-10 V (dc) or 4-20 
mA signal proportional to the boiler operating temperature. 
The RoomResponse

TM

 signal is a DOE compliant method 

of controlling boiler temperature to building load. The 
RoomResponse

TM

 signal is not available to on/off boilers.

Benefits of the RoomResponse

TM

 signal include:

•  Increase in boiler efficiency
•  Reduction in room temperature swing
•  Reduction in expansion noises from heating pipes

Mod Max % Dial

The upper limit of the 0-10 V (dc) or 4 -20 mA signal to 
the modulating condensing boiler can be set using the 
Mod Max % Dial.
This sets the upper temperature limit for the boiler.

The dial is only applicable to controls set as the Master.

Mod Max %

Max Voltage

Max mA

50

5

12

60

6

13.6

70

7

15.2

80

8

16.8

90

9

18.4

100

10

20

FUSE 6

70 80

90

60

50

100

MOD MAX %

Mod Max % dial set to 100% in the illustration.

Boiler Make/Model

Required Adapter

(Supplied by boiler 

manufacturer)

0-10 V (dc) /

4-20 mA

DIP Switch

Mod Max % Dial for Boiler Design Temperature

120°F

140°F

160°F

180°F

Aerco AM series

Not required

0-10 V

50%

65%

80%

100%

Bosch Greenstar

ICM Module

0-10 V

55%

70%

80%

100%

Buderus GB142, GB162

EM10 Module

0-10 V

50%

60%

75%

90%

Burnham

®

 Alpine

*

Not required

4-20 mA

50%

70%

85%

100%

Camus

®

 Modulating Micoflame

®

Not required

0-10 V

50%

60%

70%

85%

HTP Elite

Not required

0-10 V

50%

65%

80%

90%

IBC VFC and SL series

*

Not required

0-10 V

65%

75%

85%

100%

Laars

®

 Mascot LX

Not required

0-10 V

55%

70%

85%

100%

Laars

®

 Mascot FT

Not required

0-10 V

50%

65%

80%

100%

Lochinvar

®

 Knight

Not required

0-10 V

55%

70%

85%

100%

Lochinvar

®

 FTXL

*

Not required

0-10 V

55%

70%

85%

100%

NTI Trinity Fire Tube and LX

Not required

4-20 mA

55%

65%

75%

90%

Peerless PureFire

PFA-1 Adapter

0-10 V

55%

65%

75%

90%

Raypak Xfyre, Xtherm, MVB, XPakFT

Not required

0-10 V

55%

65%

80%

90%

Riverside HeatStation

*

Not required

0-10 V

50%

65%

85%

100%

Viessmann 100-W, WB1B

OpenTherm Module

0-10 V

55%

70%

85%

100%

Viessmann 200-W, B2HB and 300 CU3A

Not required

0-10 V

50%

60%

70%

80%

Weil-McLain

®

 Evergreen

*

Not required

0-10 V

50%

70%

85%

100%

* Requires changes to boiler's settings

Setting the Max Mod % Dial

Summary of Contents for Switching Relay 303P Series

Page 1: ...ting to a zoned hydronic heating system RoomResponseTM signal Compatible with all low voltage thermostats Unlimited zone expansion Zone priority Priority override Pump exercising Post purge Away signal shared between tekmar thermostats Features LED for each zone priority end switch and RoomResponseTM Four ground screws Top bottom and back conduit knockouts Fuses protect transformers and pumps Two ...

Page 2: ... if not avoided could result in minor or moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Read manual and all product labels BEFORE using the equipment Do not use unless you know the safe and proper operation of this equipment Keep this manual available for easy access by all users Replacement manuals are av...

Page 3: ...screwdriver Needle nose pliers Wire stripper 18 AWG LVT solid wire low voltage connections 14 AWG solid wire line voltage connections Four 1 8 1 wood screws 1 Switching Relay 302P 2 Spare fuses located in cover Installation Manual 302P_D Keep the control dry Avoid potential leakage onto the control Maintain relative humidity less than 90 in a non condensing environment Avoid exposure to extreme te...

Page 4: ...cable Away C R Rh W R W 70 FUSE 2 FUSE 7 FUSE 8 FUSE 3 FUSE 4 FUSE 5 FUSE 6 70 80 90 60 50 100 MOD MAX MASTER MEMBER OFF OFF OFF 4 20 mA T STAT 1 PRIORITY 0N EXERCISING ON POST PURGE ON MOD BOILER 0 10V RESERVED FUSE 1 120 VAC POWER MOD X X tN4 POWER ROOM RESPONSE T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 PRIORITY PUMP 1 PUMP 2 PUMP 3 PUMP 4 PUMP 5 PUMP 6 L N L N L N L N L N ...

Page 5: ...ot required Away C R Rh W 70 FUSE 2 FUSE 7 FUSE 8 FUSE 3 FUSE 4 FUSE 5 FUSE 6 70 80 90 60 50 100 MOD MAX MASTER MEMBER OFF OFF OFF 4 20 mA T STAT 1 PRIORITY 0N EXERCISING ON POST PURGE ON MOD BOILER 0 10V RESERVED FUSE 1 120 VAC POWER MOD X X tN4 POWER ROOM RESPONSE T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 PRIORITY PUMP 1 PUMP 2 PUMP 3 PUMP 4 PUMP 5 PUMP 6 L N L N L N L N L ...

Page 6: ...10V RESERVED FUSE 1 120 VAC POWER MOD X X tN4 POWER ROOM RESPONSE T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 PRIORITY PUMP 1 PUMP 2 PUMP 3 PUMP 4 PUMP 5 PUMP 6 L N L N L N L N L N L N L N tN4 A C R W tN4 A C R W T STAT 4 tN4 A C R W T STAT 5 tN4 A C R W T STAT 6 EXPANSION tN4 A C R W tN4 A B C D E FUSE 2 FUSE 7 FUSE 8 FUSE 3 FUSE 4 FUSE 5 FUSE 6 70 80 90 60 50 100 MOD MAX MAST...

Page 7: ... Switching Relay set to Master When using multiple Switching Relays and or Zone Valve Controls set one control to Master and set all other controls to Member The boiler end switch XX only closes when the DIP switch is set to Master and does not close when set to Member T Stat 1 Priority DIP Switch When T Stat 1 is calling for heat by closing the R and W terminals 115 V ac is applied to the zone 1 ...

Page 8: ...e Master Mod Max Max Voltage Max mA 50 5 12 60 6 13 6 70 7 15 2 80 8 16 8 90 9 18 4 100 10 20 FUSE 6 70 80 90 60 50 100 MOD MAX Mod Max dial set to 100 in the illustration Boiler Make Model Required Adapter Supplied by boiler manufacturer 0 10 V dc 4 20 mA DIP Switch Mod Max Dial for Boiler Design Temperature 120 F 140 F 160 F 180 F Aerco AM series Not required 0 10 V 50 65 80 100 Bosch Greenstar ...

Page 9: ... Change Energy Management setting Central Heat Modulation Source to 4 20 mA Change Energy Management setting Central Heat 4 20 mA Setup 4 mA Water Temperature to 80 F 26 5 C 9 10 22 23 5 6 16 17 2 U 1 X X T T 1 2 9 10 No changes to the boiler are required On the V10 controller Set Load 1 to External Control Change Max Control 9 5 Vdc to 190 F 88 C Change Min Control 2 1 Vdc to 32 F 0 C IBC V10 Con...

Page 10: ...etpoint source to 4 20mA Enter boiler password Set Parameter Setpoint source to 4 20mA Lochinvar Knight Lochinvar FTXL NTI Trinity LX Riverside HeatStation NTI Trinity Fire Tube 302P 302P 302P 302P 302P Sensor I O 24Vac I O X X W R 1 2 37 38 X X W R 21 22 35 36 X X CH1 R 3 5 11 12 X X CH1 R 3 5 4 5 8 EMS 9 Laars Mascot FT Peerless Pinnacle Terminal Strip Peerless Pinnacle Control Board Peerless PF...

Page 11: ...P 302P 302P 1 4 1 2 5 6 Connect to the Viessmann Extension Module EA1 Plug 0 10V Switching Relay 302P Two Zones with Priority Literature Submittal 302P_C Installation Manual 302P_D Job Record 302P_J Packaged weight 5 0 lb 2250 g Dimensions 8 3 16 H x 10 11 16 W x 2 3 8 D 208 x 271 x 60 mm Enclosure Cover ABS plastic Base galvanized steel NEMA type 1 Approvals CSA C US RoHS Ambient conditions Indoo...

Page 12: ... made by Pur chaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser s sole responsibility and obligation Purchaser shall indemnify and hold tekmar harmless from and against any and all claims liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers ...