Gas detector in metal housing (Group II protection mode, category 3G, Ex nA IIC T6) with 
operating status indicator light, for indicating gas alarms by means of a 4-20 mA analogue 
output or a trip threshold (pre-alarm, level 1 and 2 alarm, fault) that can be freely set with DIP 
switches. Power supply: 11-28 VDC. Signal output: 4-20 mA. An explosion-proof version is 
available to order, marked with the ATEX hexagon symbol and designation II 2G, Ex d IIC T6.

Compliant with Directives EMC 2014/30/EU and ATEX 2014/34/EU. 
 

 

  II 3G, Ex nA IIC T6. 

UR20S

Type

Part No.

DN

Protection

Weight (Kg)

UR20S

0940571

NATURAL GAS

IP55

0.65

UR20S

0940572

LPG

IP55

0.65

UR20S

0940573

CO

IP55

0.65

UR20S Series

 gas detectors are used for detecting inflammable or toxic gases in classified areas in industrial environments 

and boiler rooms. All models can be used with 

CIVIC1 Series

 control units (one sensor) and 

CIVIC4

 

Series 

control units (up 

to 4 sensors) or with other control units set up to receive a 4-20 mA signal (generally combined fire/intrusion detection systems).

Description

Technical features

Natural gas and LPG

Carbon monoxide

Sensor type

Standard catalytic, pellistor 

or semiconductor

Electrochemical cell

or semiconductor

Power supply

11-28VDC

11-28VDC

Maximum power consumption

3.2 W

1.5 W

Measuring range

0-100% LEL

0-500 ppm

Precision (excluding semiconductor)

+ 5% of full scale, + 10% of reading

Precision (semiconductor) 

+ 10% full scale (at setpoint)

Measurement resolution

1% LEL

5 ppm

Microprocessor resolution

1024 pixels (10 bit)

1024 pixels (10 bit)

Safety circuit

Internal watchdog

Warm-up time

< 2 mins.

< 2 mins.

Stabilisation time

< 2 mins.

< 2 mins.

Maximum response time

 < 20s (T50), < 60s (T90)

Average service life of sensor in air

255 weeks

255 weeks

4

-

20 mA output signal:

Proportional output signal 

4mA = 0% LEL

4mA = 0 ppm

(default) 

20mA = 100% LEL

20mA = 500 ppm

Threshold-based output signal 

0mA = no alarm

0mA = no alarm

(applications with 1 or 2 thresholds) 

           

10mA = 1st threshold = 20% LEL

10mA = 1st threshold = 100 ppm

20mA = 2nd threshold = 40% LEL

20mA = 2nd threshold = 200 ppm

4-20mA output reference selection 

jumpers with ref. to power supply negative or positive

Fault sensor

22 mA

22 mA

4-20mA output load resistor

< 200Ω at 12VDC power supply

< 200Ω at 12VDC power supply

200Ω-700Ω at 24VDC power supply

200Ω-700Ω at 24VDC power supply

Ambient temperature (°C):

Operation 

-20÷50°C

-20÷50°C

Storage 

-20÷70°C

-20÷70°C

Ambient relative humidity:

Operation 

15%-90% non-condensing

15%-90% non-condensing

Storage 

45%-75% non-condensing

45%-75% non-condensing

Operating pressure 

80-110 kPa

80-110 kPa

Ambient air speed

< 6 m/s

< 6 m/s

2

Watts Water Technologies, Inc.