Box Wattsense - Installation Guide
13 / 23
• Check that the ETH1 or ETH2 LED lights up.
• Connect all equipment to the switch via the Ethernet cables.
To configure each of the equipment
• Using the technical documentation of the equipment, find its IP address and TCP port (and if necessary, for some devices, the
address of the slave "Slave ID").
• If the equipment does not have an IP address, assign one to it, 192.168.1.1 for the first device, then 192.168.1.2 for the second
device, 192.168.1.3 for the third device, and so on.
• Write down the IP address and TCP port (and if necessary, for certain devices, the address of the Slave ID), the brand and model
of the equipment, and any information that allows it to be identified. This information will be necessary for the installation
configuration and to retrieve data.
5.2 The equipment communicates in Modbus RTU (RS485)
Organization of the Bus architecture:
• Gather the necessary information for each device: Bus speed, character size, parity bit, stop bit (from the user console’s
configuration wizard, get the manufacturer’s technical documentation, or directly from the control panels of the equipment).