SPECIFICATIONS

HB-480R2 Power Module

Voltages  . . . . . . . . . . . . . . . . . . . . . . . . . .347/480VAC, 60Hz
Load Requirements

@ 480VAC, 60Hz . . . . . . . . . . . . . . . . . . .1200W ballast
@ 347VAC, 60Hz . . . . . . . . . . . . . . . . . . .1200W ballast

US Patents:   . . . . . . . . . .4,787,722 • 4,874,962 • 5,124,566

* x indicates Control Module/Lens  number. See Coverage Guide.

H B - 4 8 0 R 2 - x *

High Bay • Line Vo l tage • Pa ss i ve Infra red  

O ccupancy Sensor Power Module

IMPORTANT START-UP INFORMATION

When the control module is installed and power is connected, it may take up
to a minute before the lights turn on due to a sensor warm-up period required
during initial power-up. This occurs during installation or after a power failure
of 5 minutes or more only.

If the power module is installed and powered, and no control module is in
place, the load comes on and remains on until the control module is installed.

DESCRIPTION AND OPERATION

The HB-480R2-x occupancy sensors turn lighting on and off based on
occupancy. They are designed for warehouse and high bay applications.

Careful consideration must be given to sensor placement. Avoid placing the
sensor where shelving or other obstructions may block the sensor’s line of
sight.

The HB sensors are modular and are made up of two parts, a Power Module
(HB-480R2) and a Control Module (HB-x). The HB-480R2 operates at 480VAC
or 347VAC, 60 Hz. 

COVERAGE

Coverage patterns, density and range, are determined by the type of Control
Module attached to the HB-480R2.  

For a complete description of each Control Module’s coverage pattern, see
the HB-x Control Module COVERAGE GUIDE.

Fig 1:

Ceiling Mount Assembly

Fig 2:

Fixture Mount Assembly

Control Module 

(HB-2 shown)

HB-480R2 

Power Module

Junction Box

Fixture 

CP-1 J-Box 

Adapter 

Plate

1.

Connect the existing wires to the sensor
leads.

• Do not allow bare wire to show.

• Make sure all connections are secure.

2.

Remove the Control Module from the 
HB-480R2 as shown in Fig. 7.

3a. Ceiling Mount (See Fig. 1):

• Secure the CP-1 J-Box adapter plate

to the junction box.

• Attach the sensor to the adapter plate

using four #6 x 

3

/

4

” self tapping screws.

3b. Acoustic Tile or Fixture (See Fig. 2): 

• Cut a hole in the mounting surface

using the “HB Cut-Out” template. 

• Use four #6 x 

3

/

4

” self tapping screws

to attach the sensor to the mounting
surface.

4.

Reconnect the Control Module onto the 
HB-480R2 as shown in Fig. 4.
• CAREFULLY align the four connector

pins on the HB-480R2 with the 
receptacles on the Control Module. 

• Snap the HB-480R2 Power Module to

the Control Module using firm pressure
until they click into position at the top
and bottom.

5.

Restore power from the circuit breaker.

INSTALLATION

Fig 3:

Flying lead 
c o n n e c t i o n s

Fig 4:

Connecting the
C o n t rol Module to the
H B-480R2 Power Module.

CAUTION

TURN THE POWER OFF AT THE CIRCUIT

BREAKER BEFORE INSTALLING THE SENSOR.

Fig 5: 4 8 0 VAC wiring

WIRING

Fig 6: 3 4 7 VAC wiring

MOUNTING THE SENSOR