LMRC-101

Digital Lighting Management (DLM)

Single Relay Room Controller

Quick Start GuideQuick Start Guide

Room

Controller

J Box

Corner Mount

Occupancy

Sensor

Switch

To

Load/Line

(Class 1 wiring)

DLM Local Network 

(low voltage, Class 2)

LMRJ Cables

PLACEMENT EXAMPLE

CONNECTIVITY

The LMRC-101 communicates to all other DLM 
devices connected to the DLM Local Network. 
Connection drawings are for example only. The low 
voltage LMRJ cables can connect to any DLM device 
with an open RJ45 receptacle.

All line voltage wiring is #12 AWG.

Line

Voltage

Room

Controller

J-Box

Daylight Sensor

Switch

Ceiling Mount

Sensor

DLM Local Network

Low Voltage

LMRJ Cables

Load

Line/Hot

Black wire

Neutral

White wire

Red wire

to Load

LMRC

101

Switch

ATTACHING CABLES

MOUNTING THE CONTROLLER

The LMRC-101 room controller can either be mounted 
external to a junction box, placing it in the plenum space or 
mounted directly inside a 4” x 4” junction box. 

    Outside  a  4”  x  4”  box                                                  Inside  a  4”  x  4”  box                                            

Remove rubber jack covers if using all 3 RJ45 receptacles. 
Leave covers in place for all unused receptacles.

Input Voltage:. . . . . . . . . . . . . . . . . . . . . . . .120/230/277VAC, 50/60Hz

Load Requirements:
 

Incandescent  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  20A @ 120VAC

 

Ballast. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20A @ 120/277VAC

 

Motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1Hp @ 120/240VAC

Output    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150mA @ 24VDC

DLM Local Network Characteristics:
 

Provides low voltage power over Cat 5e cable (LMRJ).

 

Supports up to 24 communicating devices, including 4 

 

LMRC-10x or LMPL-101 max per each DLM Local Network.

 

Free topology up to 1,000ft of low voltage cable.

Environment:
 

Operating Temperature. . . . . . . . . . . . . .32° to 104°F (0° to 40°C)

 

Storage Temperature  . . . . . . . . . . . . . . 23° to 176°F (-5° to 80°C)

 

Relative Humidity. . . . . . . . . . . . . . . . . 5 to 95% (non condensing)

Patent Pending

Line

J-Box

Load

J-Box

Load

Line

WARNING:

 TO CONNECT A COMPUTER TO THE DLM 

LOCAL NETWORK USE THE LMCI-100.  

NEVER CONNECT THE DLM LOCAL 

NETWORK TO AN ETHERNET PORT

 – 

IT MAY DAMAGE COMPUTERS AND 

OTHER CONNECTED EQUIPMENT.

CAUTION:

 TURN THE 

POWER OFF AT THE CIRCUIT 

BREAKER BEFORE WIRING.

THIS UNIT IS PRE-SET FOR PLUG n’ GO™ 

OPERATION, ADJUSTMENT IS OPTIONAL.

For full operational details, adjustment and more 

features of the product, see the DLM System Installation 

Guide provided with the LMRC-102 room controller, 

and also available at 

www.wattstopper.com 

INSTALLATION SHALL BE IN ACCORDANCE WITH ALL 

APPLICABLE REGULATIONS, LOCAL AND NEC CODES.

Wire connections shall be rated suitable for the wire 

size (lead and building wiring) employed.

For Class 2 DLM devices and device wiring:

 

To be connected to a Class 2 power source only. 

 

Do not reclassify and install as Class 1, or Power and Lighting Wiring.

 WARNING:

 Do not install to cover a junction box having Class 1, 3 or 

Power and Lighting Circuits.

Reviews: