HPSA-7100-R Series Installation and User Manual
135
P/N P01-04946-C
Combination FACP/SP40S and Multiple HPSA-7100-Rs
A.8
COMBINATION FACP/SP40S AND MULTIPLE HPSA-7100-R
S
FIGURE A.10
Combination FACP/SP40S and Multiple HPSAs
NOTES for Figure A.10, Combination FACP/SP40S with Multiple HPSAs:
1.
The Combination FACP/SP40S application requires an SP4Z-A/B Speaker Audio Splitter, shown
with four independent Class B audio zones (refer to the SP40S Manual for Class A wiring). One
zone (the Audio circuit) must be dedicated for HPSA connectivity, the remaining zones can be
used for in building applications or additional HPSAs wired directly from the SP40S. Refer to the
SP40S Installation, Testing, Operations and Maintenance Manual, P84714
, for details.
2.
In the Combination application, the PTT/Trouble contacts are controlled and monitored directly
from the FACP using the dry contact interface. In this application, the activation of the HPSA
utilizes a single dry contact from the FACP. Refer to the FACP’s Instructions Manual for proper
wiring and programming of the dry contact.
3.
The trouble contacts on the HPSA’s AMB can be configured for normally open (NO) or normally
closed (NC) depending on the configuration of the FACP.
4.
End-of-Line resistors (EOLR), (not shown in the
Audio In
line), shall be connected at the furthest
HPSA. Verify the SP40S and HPSA are configured for the same output voltage settings prior to
energizing the system; failure to configure the same setting could damage the HPSA.
5.
Multiple HPSAs can be controlled from a single SP40S. EOLR, are not shown in the figure,
however, an EOLR must be connected on the Audio In and Trouble Contact on the furthest
HPSA. When connecting to the HPSAs, break the wire runs at each terminal block on the HPSA,
DO NOT loop the wire under the terminals.
6.
Dedicated circuits are required on all audio, control and monitoring lines. Additional circuits from
the SP4Z-A/B are available for in building (or other) applications.
7.
For FACO operation, each monitored Trouble contact must have an EOLR across the terminals.
8.
Refer to the FACP manufacturer’s Instructions and the
SP40S Installation, Testing, Operations
and Maintenance Manual, P84714
, for details regarding cable connections and pin outs.
Summary of Contents for HPSA-7100-R Series
Page 2: ...This page intentionally left blank...
Page 10: ...viii HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 16: ...xiv HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 20: ...xviii HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 22: ...xx HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 26: ...Preface xxiv HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 33: ...HPSA 7100 R Series Installation and User Manual 7 P N P01 04946 Rev C System Components...
Page 34: ...Introduction 8 HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 58: ...Installing the Cabinet 32 HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 174: ...148 HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 178: ......